Table 14:
Configuration 1 / 9 Parameter Details.
Configuration Parameters Default Value
Significance and Adjustments
VAV Box Type
Default value: PI
PI: Pressure Independent.
PD: Pressure Dependent.
Choices: PI, PD.
Flow @ 1 in. wc (Flow at 1-inch
Water Column)
Default Value: 800 CFM (377 l/s)
Displayed when PI VAV box type is selected.
Range: 150 CFM (71 l/s) to 7500 CFM (3540 l/s), using 10 CFM (5 l/s) increments.
Pressure Range
Default Value: 1.0 in. wc (250.0 Pa)
Displayed when PI VAV box type is selected.
Range: 0.5 in. wc (125 Pa) to 5.0 in. wc (1250 Pa), using 0.5 in wc (125 Pa) increments.
Actuator Type
Default Value: 0-10V DA
Output type used to control the damper actuator.
Choices: 0-10V DA, 0-10V RA, 2-10V DA, 2-10V RA, Floating.
Actuator Time
Default Value: 1.5 min.
Displayed when PI VAV box type is selected, or when PD VAV box type and Floating
Actuator type are selected.
Time for floating actuator to transition between fully closed and fully open.
Range: 0.5 min to 9.0 min, using 0.5 min increments.
1/9 Configuration
VAV box type
PI
Flow @ 1 in. wc
800 CFM
Pressure range
1.0 in. wc
Actuator type
0-10V DA
Actuator time
1.5 min
Configuration 1 / 9
CONFIGURATION SCREENS
Configuration 1 / 9
Figure 22:
Configuration 1 / 9 Displays.
See “Display 2 / 3” on page 52 for infor-
mation on how to switch between the SI
and Imperial measurement system.
1/9 Configuration
VAV box type
PD
Actuator type
Floating
Actuator time
1.5 min