BACnet Network Settings
BACnet network screen shows when BACnet MS/TP is selected in wired protocol parameter.
Table 6: BACnet Network Parameter Details.
Configuration Parameters Default Value
Significance and Adjustments
Comm address (Communication
Address)
Default value: 254
Room Controller networking address.
Default value of 254 disables BACnet communication for the Room Controller.
Range: 0 to 254
Network Units (Measurement Units)
Default Value: SI
Network units transmitted over the BACnet network.
Use the Temperature scale parameter to change the display units locally on the Room Controller.
Imperial: Network units shown as Imperial units.
SI: Network units shown as International Metric units.
Choices: Imperial or SI
Network Language
Default Value: English
Network language/object names transmitted over network.
Choices: English, French or Spanish
Baud Rate (BACnet Baud Rate)
Default Value: Auto
Leave the value at Auto unless instructed otherwise as this automatically detects BACnet
baud rate.
Choices: Auto, 115200, 76800, 57600, 38400, 19200, and 9600.
BACnet Status
Read Only
Read Only value shows if a BACnet Network is detected or not.
Display Readings: Online or Offline
BACnet PRate (BACnet Poll Rate)
Default Value: 4
Rate at which a BACnet stack is processed, in milliseconds.
Range: 1 to 5.
NETWORK SCREENS
BACnet Network Settings
Figure 12: BACnet Network Display.
1/2 BACnet Network
Baud rate
Auto
Network units
SI
Network lang.
English
BACnet status
Offline
BACnet PRate
4
COM address
254