MultiSITE MS8250 V

AV Room Controllers

Due to our policy of continuous product innovation, some specifications may change without notification.  

©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.

2/2 Setup

Test Outputs

Language Selection

Clock - Schedule

ADR

Wireless

Lua

Set Clock, Schedule and Occupancy

LUA Scripting (Shows Only if LUA Script is Uploaded)

Wireless Ecosystem Settings (shows only if ZigBee feature is available)

Test Output Settings

HMI DISPLAY AND SET UP

Figure 4: Set-up Screen Display 2 / 2.

Select Language

Automatic Demand Response

Содержание MultiSITE MS8250

Страница 1: ...USER MANUAL MultiSITE MS8250 VAV Room Controller MS8250 Model No VUCQMS8250 Variable Air Volume VAV Controller ...

Страница 2: ...or proper installation For more technical materials such as submittals engineering databooks and catalogs visit www lghvac com For continual product development LG Electronics U S A Inc reserves the right to change specifications without notice LG Electronics U S A Inc This document as well as all reports illustrations data information and other materials are the property of LG Electronics U S A I...

Страница 3: ...Configuration Screens 32 42 Configuration 1 9 32 Configuration 2 9 33 Configuration 3 9 34 Configuration 4 9 35 Configuration 5 9 36 37 Configuration 6 9 38 Configuration 7 9 39 Configuration 8 9 40 41 Configuration 9 9 42 Balancing 43 48 Pressure Independent 43 46 Pressure Dependent 47 48 Setpoints Screens 49 50 Setpoints 1 2 49 Setpoints 2 2 50 Display Screens 51 53 Display Screen 1 3 51 Display...

Страница 4: ...with tools or exposed skin Only quali fied technicians should install use or remove this unit Improper installation or use may result in fire explosion electric shock physical injury and or death WARNING The information contained in this manual is intended for use by an industry qualified experienced trained electrician familiar with local national and regional codes and who is equipped with the p...

Страница 5: ...iquid on the inside of the con troller Do not drop the controller into water If the unit is immersed in water or other liquid contact your local autho rized LG distributor for support There is risk of unit failure or degraded performance This device is only intended for use as a monitoring and control device It is not a safety device Do not use it for any other purpose Tampering with the devices o...

Страница 6: ...rt 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a p...

Страница 7: ...o follow instructions will result in operation malfunction 1 For additional information about anticipated transmission delays or failures of the link refer to NEMA ICS 1 1 latest edition Safety Guidelines for the Application Installation and Maintenance of Solid State Control or its equivalent California Proposition 65 This product can expose you to chemicals including Lead and Bisphenol A BPA whi...

Страница 8: ... digital touch screen interface with multi language support BACnet Available BACnet options listed under Connectivity or Modbus On Board ZigBee Communication Module Automatic Demand Response ADR used to reduce energy load when electric grid contingencies threaten supply demand balance Custom LUA script can be uploaded to the VAV Room Controller Passwords can be set to prevent unauthorized user acc...

Страница 9: ...Standby screen selection from the setup menu Display 1 2 This setting switches the display during periods of inactivity from the Home Screen It is recommended to use a black or medium gray image or one with light color contrasts as the screen saver to prevent this phenomenon from occurring If the display still exhibits this phenomenon loading an all black or all medium gray image as the screen sav...

Страница 10: ...itality industry The User HMI is configurable and allows display functions such as Date Time Humidity Outdoor Temperature and Setpoint to be enabled or disabled by setting various parameters HMI DISPLAY AND SET UP Figure 1 Typical Hospitality Industry User Interface Time Language Select Preferred Language Unoccupied Mode Override Date Occupancy Status Room Indoor Temperature Room Indoor Humidity O...

Страница 11: ...s point for three 3 seconds to enter set up mode If a configuration installer password is activated to prevent unauthorized access to the configuration menu parameters a password entry prompt appears before proceeding 1 2 Setup Network Configuration Balancing Setpoints Display Service View BACnet MS TP Modbus and ZigBee and Wi Fi Network Settings network settings ZigBee network settings appear onl...

Страница 12: ...rved LG Life s Good is a registered trademark of LG Corp 2 2 Setup Test Outputs Language Selection Clock Schedule ADR Wireless Lua Set Clock Schedule and Occupancy LUA Scripting Shows Only if LUA Script is Uploaded Wireless Ecosystem Settings shows only if ZigBee feature is available Test Output Settings HMI DISPLAY AND SET UP Figure 4 Set up Screen Display 2 2 Select Language Automatic Demand Res...

Страница 13: ...tpoint adjustment System mode setting User help menu Setpoint adjustment Local unit scale adjustment Local user language User help menu Setpoint adjustment User help menu Parameters are model dependent and may not appear on certain models 2019 08 19 12 54 PM F 2019 08 19 12 54 PM F 2019 08 19 12 54 PM F Fully locked interface with no user settings Setpoint adjustment System mode setting User help ...

Страница 14: ...al 9 Commercial 10 2019 08 19 12 54 PM F Setpoint adjustment System mode setting Unoccupied mode override User help menu Commercial 11 User HMI for Commercial 2019 08 19 12 54 PM Commercial 12 Offset setpoints adjustment System mode setting Local user language Fan mode setting User help menu CUSTOMIZED SCREENS Parameters are model dependent and may not appear on certain models The day night setbac...

Страница 15: ...us fan status or help button Each show hide option is applicable to all User HMI configurations where the option is shown To hide the option select disabled for each display setup screen parameter Refer to the Display Screens Section Options Enabled Options Disabled Fan Status System Status Help Button Table 1 System Mode Descriptions System Mode Significance and Adjustments System Mode Off Off He...

Страница 16: ...onal CO2 detection sensor module or a wireless sen sor end device selected by the CO2 source parameter on the setup configuration screen Outdoor temperature shows when receiving a valid networked outdoor temperature value or a temperature sensor connected to UI23 Setpoint Adjustment During occupied setpoint adjustment large digits are temporarily used to display the occupied setpoint Use the up an...

Страница 17: ...ered trademark of LG Corp Customizable Color Options CUSTOMIZED SCREENS Customizable Color Options Figure 7 Display Color Options White Green Blue Dark Grey Pink Grey Purple Red Orange Black 2019 08 19 12 54 PM F 2019 08 19 12 54 PM F 2019 08 19 12 54 PM F 2019 08 19 12 54 PM F 2019 08 19 12 54 PM F 2019 08 19 12 54 PM F 2019 08 19 12 54 PM F 2019 08 19 12 54 PM F 2019 08 19 12 54 PM F 2019 08 19 ...

Страница 18: ...on the Setup screen shows only if a LUA script is uploaded to the Room Controller Figure 8 Legend Screen Details When any change is made to a parameter the value is automatically saved in memory when the next parameter is selected or another screen is opened This event is true only if a parameter was changed locally on the Room Controller making changes through BACnet will not have the same outcom...

Страница 19: ...Read Only Requires onboard ZigBee module or optional Wi Fi module VCM8002V504 ZigBee ZigBee detected IP Wi Fi module detected BAC IP Wi Fi module detected and BACnet IP enabled Display Readings ZigBee IP or BAC IP Wired Protocol Default Value BACnet None No wired protocol configured BAC MSTP BACnet MS TP network protocol Modbus Modbus network protocol Choices None BACnet or Modbus NETWORK SCREENS ...

Страница 20: ...quency on which the ZigBee network transmits and receives data The channel of the Coordinator must match that of the routers to exchange data The default value of 10 is NOT a valid channel and causes ZigBee to be disabled The valid range of available channels is from 11 to 25 Using channels 15 20 and 25 is recommended Channel 25 is considered as being the best one because it is furthest from the W...

Страница 21: ...f ZigBee 3 0 This means that legacy ZigBee Home Automation 1 x devices cannot join a Normal security network Compatible with the SEDC02G5045 sensor Selecting the Normal Security option will result in the removal of legacy sensors from the network Choices Low or Normal Network Status ZigBee Network Status Read Only Shows the current status of the ZigBee network No NWK ZigBee configured but no netwo...

Страница 22: ...ce on the network and is recommended if used with an MPM It is Mandatory for BACnet Range 0 to 254 Short Address ZigBee Short Address Default Value 0 Read Only The unique ZigBee address is generated once device joins a ZigBee network IEEE Address Read Only The extended IEEE address MAC address is a unique worldwide identifier of the on board ZigBee or optional ZigBee add on module ZigBee Revision ...

Страница 23: ...le parameter to change the display units locally on the Room Controller Imperial Network units shown as Imperial units SI Network units shown as International Metric units Choices Imperial or SI Network Language Default Value English Network language object names transmitted over network Choices English French or Spanish Baud Rate BACnet Baud Rate Default Value Auto Leave the value at Auto unless ...

Страница 24: ...enerated by the model number and COM address of the Controller For example the instance number of the VUCQMS8250 with a COM address of 57 is generated as 82057 The default instance number appears first To change the instance number use number pad and press Accept and Save Tap R icon to reset to automatic instance addressing 0 8 2 0 0 5 7 2 2 BACnet instance Instance Number of Controller Accept and...

Страница 25: ...st have a unique ad dress Other values not recommended for Modbus Default value of 254 disables Modbus communication for the Controller Range 0 to 254 Network Units Measurement Units Default Value SI Network units transmitted over the Modbus network Use the Temperature scale parameter to change the display units locally on the Room Control ler Imperial Network units shown as Imperial units SI Netw...

Страница 26: ...nt status of the Wi Fi module It would normally display Ready when the Wi Fi module is operational Status value Offline Booting Initializing Ready Fail Wi Fi Network 1 5 The Wi Fi Network screen shows only in models with optional Wi Fi module VCM8002V504 MAC address 90 70 65 f9 06 16 Device name rc8X00_0617 Module status Ready 1 5 Wi Fi Firmware version 1 0 1 B12 Push to Restart Wi Fi The Device N...

Страница 27: ... Point cre ated by the Wi Fi module Add the device to this network to access the Configuration Web Page The password needed to connect to the Access Point Wi Fi network When connected to the Access Point browse to this IP address to access the Configuration Web Page NETWORK SCREENS Wi Fi Network 2 5 Figure 16 Wi Fi Network 2 5 Display Table 9 Wi Fi Network 2 5 Parameter Details Configuration Param...

Страница 28: ...will be displayed as Ready or Online if it has an internet connection Status value Idle Connected Associate Config Ready Online Disconn Failure Signal Strength Read Only Signal strength of the Wi Fi network Range 0 to 100 SMTP status Read Only Status of the email SMTP server Status value Disabled Offline Online IP address 192 168 171 40 dhcp SSID Your Wi Fi Network Wi Fi status Online Signal stren...

Страница 29: ...ility Expert Enabled Status Online 4 5 Wi Fi Facility Expert Configuration Parameters Default Value Significance and Adjustments Facility Expert Read Only Shows whether the Facility Expert system is Disabled or Enabled Status value Disabled or Enabled Status Read Only Shows the current status of the Facility Expert system Range Disabled Offline Connect Online Failure Unknown Table 11 Wi Fi Network...

Страница 30: ... be reset to original Table 12 Wi Fi Network 5 5 Parameter Details Configuration Parameters Default Value Significance and Adjustments Factory reset Erase All Default Value No Accepting Yes for both and then tapping Push to accept will restore the Wi Fi module to the factory settings erase all configuration data and revert the Wi Fi Module Firmware to the factory firmware version If the password f...

Страница 31: ... first To change the instance number use number pad and press Accept and Save Tap R icon to reset to automatic instance addressing 1 2 BACnet Network Network lang English Port 0x0000 Network units SI 0 8 2 0 0 5 7 2 2 BACnet instance Instance Number of Controller Accept and Save Reset to Automatic Instance Addressing Figure 20 BACnet Network Settings Display Figure 21 BACnet Instance Setting Displ...

Страница 32: ...VAV box type is selected Range 0 5 in wc 125 Pa to 5 0 in wc 1250 Pa using 0 5 in wc 125 Pa increments Actuator Type Default Value 0 10V DA Output type used to control the damper actuator Choices 0 10V DA 0 10V RA 2 10V DA 2 10V RA Floating Actuator Time Default Value 1 5 min Displayed when PI VAV box type is selected or when PD VAV box type and Floating Actuator type are selected Time for floatin...

Страница 33: ... Significance and Adjustments Fan Type Default Value None Fan type configuration determines the fan control method Choices None Par on off Ser on off Par ECM Ser ECM ECM Low Volt ECM Low Voltage Default Value 2 2 Vdc Displayed when the Parallel ECM or Serial ECM fan type is selected Range 2 0 Vdc to 4 0 Vdc using 0 1 Vdc increments ECM High Volt ECM High Voltage Default Value 8 6 Vdc Displayed whe...

Страница 34: ...Off PWM Vac Valve NC Valve NO 0 10V DA 0 10V RA 2 10V DA 2 10V RA Floating Float Heat Time Floating Heat Time Default Value 1 5 min Displayed when Floating Duct heater is selected Range 0 5 min to 9 0 min using 0 5 min increments OAT Duct Lock Default Value 60 0 F 15 5 C Outside air temperature above which duct reheat will be disabled Displayed when Duct only Duct base or Base duct is selected Ran...

Страница 35: ...nd Adjustments Heat PI Weight Heat Proportional Integral Weight Default Value 100 Zone weight for heating system demand management Range 0 to 100 using 25 increments Cool PI Weight Cool Proportional Integral Weight Default Value 100 Zone weight for cooling system demand management Range 0 and 100 using 25 increments Zone Mode Default Value Cool Type of air being delivered to the zone by the VAV sy...

Страница 36: ...n NO or Normally Closed NC remote PIR motion sensor Window Forces system to disable any current heating or cooling action by Room Control ler when window is open Choices None Rem NSB Motion NO Motion NC Window UI17 Config Universal Input Configuration No 2 Default Value None None No function associated with input Door Dry Room Controller goes to standby mode when door is opened then closed followe...

Страница 37: ... Smart Recovery Enable Smart Recovery Default Value Off Off No smart recovery The occupied schedule time is the time at which the occupancy change will be applied therefore the desired occupied temperature will not be attained until some minutes after the scheduled time On Smart recovery active The occupied schedule time is the time at which the desired occupied temperature will be attained The Ro...

Страница 38: ... F 0 5 C increments Standby Time Default 0 5 hours Time between the moment where the motion sensor detects last movement in the area and the time which the Room Controller stand by setpoints become active This parameter is not active when the Door function is used wired or wireless Range 0 5 to 24 0 hours using 0 5 hour increments Unocc Time Unoccupied Time Default 0 0 hours Time between the momen...

Страница 39: ...cess to main screen adjustments A default value of 0 will not prompt for a password Range 0 to 9999 Schedule Menu Default Value Enabled Toggles activation of schedule menu direct access Enabled Schedule Menu is directly accessible from the main screen via a touch in the upper corner Disabled Schedule Menu can only be accessed through the Setup Menu screens En no clk Schedule Menu is directly acces...

Страница 40: ...he source of the indoor room temperature This parameter allows the user to desig nate either the Room Controller or any of the paired wireless devices that support tem perature to act as the source for the room temperature Wired Sets the thermistor connected to UI20 RS as the source to report room tempera ture Internal Sets the Room Controller as the source for the room temperature WL 1 to WL 20 s...

Страница 41: ...pport humidity to act as the source for the room humidity Internal Sets the Room Controller as the source for the room humidity WL 1 to WL 20 Sets the selected ZigBee wireless device as the source for the room humidity Only one device can be selected Choices Internal and WL 1 to WL 20 CO2 Source CO2 Sensor Source Default Value Local Sets the source of the indoor CO2 This parameter allows the user ...

Страница 42: ...efault Value Significance and Adjustments Erase all Default Value No Accepting Yes for both and then tapping Push to accept returns all values to the factory default settings with the exception of the following COM address Network Units Network Language Baud Rate BACnet Instance Device Name Screen Contrast LUA Script Node type in ZigBee Network screen returns to default value Router Are You Sure D...

Страница 43: ...ensure the calculated air flow matches the true air flow Pressure Dependent True air flow at various damper position percentages will be measured and used to set the appropriate damper percentages for the air flow required for the zone Flow sensor PI only Damper Calibrated Flow Sensor Balometer Balancing menus will timeout after eight 8 hours and any Damper Override will be removed returning the z...

Страница 44: ...c airflow control depending on the system design 4 Calibrate sensor at Minimum airflow On page 2 2 Balancing PI set the Damper Override to Minimum Flow The displayed Airflow Setpoint will use the value of Minimum Airflow Wait for the Room Controller measured Airflow level to stabilize Take a reading of the actual airflow using a calibrated balometer Enter the actual airflow as the Balometer value ...

Страница 45: ... active airflow setpoint Airflow Setpoint is not displayed when Damper Over ride is Open or Closed Range 0 to 10000 CFM 0 to 4720 l s Min Flow Minimum Airflow Default value 340 CFM 160 l s AV250 R W Minimum airflow supplied to the zone Range 40 to 800 CFM 19 to 377 l s Max Cool Flow Maximum Cooling Airflow Default Value 340 CFM 160 l s AV252 R W Maximum airflow supplied to the zone when cooling Ra...

Страница 46: ... airflow setpoint 5 Open Force damper fully open Choices None Minimum Max cool Close Reheat and Open Balometer Measured Airflow From Balometer Default Value 0 CFM 0 l s N A Measured value will be used to update calibration Offset and ensure mea sured Airflow level matches Balometer reading Balometer is displayed when Damper Override is Minimum or Max cool Range 0 to 20000 CFM 0 to 9440 l s Minflow...

Страница 47: ...amper positions for Minimum Maximum Cooling Maximum Heating Reheat and Damper Override 2 For each position repeat the following process Set the Damper Override to the desired position Minimum Maximum Cooling Maximum Heating or Maximum Reheat Allow time for damper to reach defined position Take reading of actual air flow using a calibrated Balometer Compare actual airflow to desired airflow and adj...

Страница 48: ...51 R W Range 0 to 100 Max Heat Pos Maximum Damper Position During Heating Default Value 100 AV252 R W Range 0 to 100 Reheat Pos Damper Position During Reheating Default Value 30 AV253 R W Range 0 to 100 Damp Override Damper Override Default Value None MV172 R W Force damper to selected position during balancing 0 None No damper override Damper under normal control 1 Minimum Force damper to maintai...

Страница 49: ...oling Temperature setpoint used by the Room Controller when in Standby mode Range 54 to 100 F 12 0 to 37 5 C Occ Cool Occupied Cool Setpoint Default Value 75 0 F 24 0 C Cooling Temperature setpoint used by the Room Controller when in Occupied or Override mode Range 54 to 100 F 12 0 to 37 5 C Occ Heat Occupied Heat Setpoint Default Value 72 0 F 22 0 C Heating Temperature setpoint used by the Room C...

Страница 50: ... to Configuration 6 9 on page 38 to configure Standby mode Range 65 to 80 F 18 5 to 26 5 C Deadband Default Value 3 F 1 5 C Temperature offset between the Cooling and Heating setpoints to ensure that Cooling setpoint is always warmer than the Heating setpoint Cooling setpoint Heating setpoint Deadband Range 2 to 5 F 1 0 to 2 5 C Max Heating Heating Setpoint Limit Default Value 90 F 32 C Maximum Oc...

Страница 51: ... T set Standby Screen Default Value No When the device is left unattended for 150 seconds the standby image will appear A custom image can be uploaded using the Uploader Tool No No Stand by image Screen dims when no motion is detected Yes Stand by Image is displayed after 150 seconds Occ Only Standby image displays after 150 seconds Screen turns off after 30 minutes only in occupied or override mo...

Страница 52: ...econds after no activity on the Room Controller Adjustable 0 to 100 Night Backlight Default Value 5 Sets backlight display intensity Parameter only available for models with motion light detec tors The screen backlight progressively decreases down to this setting when room is dark This feature is used mostly in hospitality applications when a darker non obtrusive lighting level is desired when roo...

Страница 53: ...an status in the upper right corner of the User HMI display Applicable to all User HMI configurations where the fan status is shown Refer to the User HMI Show Hide Options on page 15 Choices Enabled or Disabled System Status Systen Status Display Default Value Enabled Hides the system status in the upper right corner of the User HMI display Applicable to all User HMI configurations where the syste...

Страница 54: ...3 Service View Screen 1 9 Parameter Details Configuration Parameters Default Value Significance and Adjustments Room Temp Room Temperature Read Only Shows the current room temperature from the configured temperature source UI19 Changeover Changeover Temperature Sensor Read Only Shows the temperature of the changeover sensor connected to UI19 terminal UI20 Temp Room Temperature Sensor Read Only Sho...

Страница 55: ...adings Occupied Unoccupied Override and Standby PI Cool Demand Proportional Integral Cooling Demand Read Only Percentage of cooling capacity demanded by the zone Display Readings 0 100 PI Heat Demand Proportional Integral Heat Demand Read Only Percentage of heating capacity demanded by the zone Display Readings 0 100 Zone Demand Read Only Combined and weighted heating cooling demand for the zone w...

Страница 56: ...ated UI19 Binary Universal Input Configuration No 3 Read Only Shows status of input Display Readings Activated or Not Activated Zigb PIR Inst ZigBee Passive Infrared Sensor Installed Read Only Shows if ZigBee motion sensor is paired to a Room Controller or not This parameter is for ZigBee wireless motion sensors only Display Readings Off or On Zigb Sens Mot ZigBee Sensor Motion Read Only Shows if ...

Страница 57: ...ows On if there is a Window alarm and shows Off if there is no Window alarm This feature is for both wired and wireless sensors Display Readings On or Off Service Alarm Read Only Shows On if there is a Service alarm and shows Off if there is no Service alarm Display Readings On or Off Filter Alarm Read Only Shows On if there is a Filter alarm and shows Off if there is no Filter alarm Display Readi...

Страница 58: ...ter Details Configuration Parameters Default Value Significance and Adjustments UO9 Config UO9 Configuration Read Only Display Readings Analog Binary Relay RC or Relay RH UO10 Config UO10 Configuration Read Only Display Readings Analog Binary or Relay RC UO11 Config UO11 Configuration Read Only Display Readings Analog or Binary UO12 Config UO12 Configuration Read Only Display Readings Analog or Bi...

Страница 59: ...onfiguration Parameters Default Value Significance and Adjustments UI19 Type UI19 Input Type Read Only Display Readings Thermistor Binary or Voltage UI20 Type UI20 Input Type Read Only Display Readings Thermistor Binary or Voltage UI22 Type UI22 Input Type Read Only Display Readings Thermistor Binary or Voltage UI23 Type UI23 Input Type Read Only Display Readings Thermistor Binary or Voltage UI24 ...

Страница 60: ...ignificance and Adjustments CO2 Eff Source CO2 Module Read Only Shows the configured source of the indoor CO2 Display Readings None Local or WL 1 to WL 20 CO2 Err Code CO2 Error Code Default Value 0 Read Only Error code 0x0001 shows if there is an error with the sensor CO2 Level Read Only Shows CO2 level in PPM Display Readings 0 to 5000 PPM CO2 FW Rev CO2 Firmware Revision Read Only Shows the Fir...

Страница 61: ... 9 Service View Screen 8 9 Figure 47 Service View Screen 8 9 Table 39 Service View Screen 8 9 Parameter Details Configuration Parameters Default Value Significance and Adjustments Eff Sys Mode Effective System Mode Read Only Shows the current operating mode of the system For example when the system is in Auto mode this parameter shows whether it is currently heating or cooling Displayed Readings C...

Страница 62: ...a the BACnet front end and the new name appears on the above screen For example when a VUCQMS8250 Room Controller with a MAC address of 41 is connected to a network its default Device Name is VUCQMS8250 41 and its default BACnet Device ID is 82041 Firmware Revision shows the Firmware version currently installed on the Room Controller Upgrading to a newer Firmware version deletes the previous Firmw...

Страница 63: ...ually enabling outputs It is the responsibility of the Installer Service Contractor to maintain a safe operation environ ment during usage There is a risk of physical injury and or death Use high caution when manually enabling outputs so as to not cause damage to equipment It is the responsibility of the Installer Service Contrac tor to maintain a safe operation environment during usage TEST OUTPU...

Страница 64: ... screen Test Outputs values are LIVE Any output gets displayed immediately for any value change according to the following 1 If any BACnet priority array 1 16 includes a value the displayed state background shows in red 2 When toggling a value on the screen the output directly energizes according to the selected value 3 After any output state gets modified all overrides get cancelled after one 1 m...

Страница 65: ...ed 3 4 Language Selection Indonesian Polish Norwegian Disabled Disabled Disabled Italian Disabled Japanese Disabled Portuguese Disabled 4 4 Language Selection Slovak Disabled Swedish Disabled Turkish Disabled Only English French Spanish Chinese and Russian are enabled by default and are accessible to users cycling through languages on the display settings menu screen To change the language selecti...

Страница 66: ...S A Inc Englewood Cliffs NJ All rights reserved LG Life s Good is a registered trademark of LG Corp Options Schedule Menu Clock Schedule Clock Settings Schedule Settings Options Settings Clock Schedule Menu The Clock Schedule Menu screen is directly accessible from the main setup screen SCHEDULE SCREENS Clock Schedule Menu Figure 52 Clock Schedule Menu Display ...

Страница 67: ...me Default Value Current time at power up Standard time display 12 hour AM PM or 24 hour format determined by the Time Format parameter value Year Default value 2019 Current year Range 2000 2100 Month Default Value Jan Current month Range Jan Dec Day Date Default Value 1 Current date Range 1 31 Weekday Current Day Default value Monday Read Only Automatically set based on data received from Year Mo...

Страница 68: ...ically set to use the Occupied setpoint There are three 3 separate Occupied parameter entries Range 00 00 23 59 Unoccupied 1 3 Default Value None Defines a time when the Room Controller is automatically set to use the Unoccupied setpoint There are three 3 separate Unoccupied parameter entries Range 00 00 23 59 Schedule There are seven 7 different schedule setting screens one 1 for each day of the ...

Страница 69: ...ed Loc occ Occupancy is determined by local sequences either PIR or schedule as config ured under Occ source Occupied Force occupied mode Unoccup Force unoccupied mode Choices Loc occ Occupied or Unocc Schedule Type Default Value 7 days 7 days Independent scheduling identified by day of the week Sunday Saturday 5 1 1 days Weekdays scheduling and Independent Weekend scheduling identified as Weekday...

Страница 70: ...initiate Load Shedding This demand can only be set through BACnet by the local Utility company using the Load Shedding Demand Binary Object Value Properties Off No Load Shedding Demand is received or the Shedding demand is disabled On Received the Load Shedding Demand or received the signal to activate Load Shedding Display Readings On or Off Shed Offset Load Shedding Offset Default Value 4 F 2 C ...

Страница 71: ...nglewood Cliffs NJ All rights reserved LG Life s Good is a registered trademark of LG Corp Alarms Configuration Wireless Ecosystem Device Groups Alarms Wireless Menu Options The Wireless screen shows only in models with onboard ZigBee or optional ZigBee add on module WIRELESS SCREENS Wireless Menu Options Figure 57 Wireless Menu Options Display ...

Страница 72: ...he network Permit join can be On Off when the Room Controller is a coordinator however the parameter is read only when the Room Controller is a router Permit join stays On for three 3 hours On Allows Room Controller to pair with wireless ZigBee device Off Prevents Room Controller from pairing with wireless ZigBee device or prevent any ad ditional ZigBee devices from joining network Choices On or O...

Страница 73: ...t Value None Shows status of installed ZigBee wireless device None No status reported to Room Controller Window Window sensor installed Door Door sensor installed Motion Device set to detect motion Env data Temperature Humidity CO2 sensor installed Remove Removes device from Device list Water Water leak sensor installed Refrig Refrigerator temperature sensor installed Freezer Freezer temperature s...

Страница 74: ...p WIRELESS SCREENS Device X Device X continued Table 46 Device X Parameter Details continued Configuration Parameters Default Value Significance and Adjustments Device Values Read Only Shows the ZigBee wireless device values Values displayed will be different depending on type of device Door and Window Sensors Closed or Open Motion Sensor No Motion or Motion Water Leak Sensor Normal or Leak Temper...

Страница 75: ...Configuration Parameters Default Value Significance and Adjustments Door Installed Door Contact Installed Default Value No Read Only Shows if Door sensor is installed Display Readings Yes or No Win Installed Window Contact Installed Default Value No Read Only Shows if Window sensor is installed Display Readings Yes or No Water Installed Water Leak Sensor Installed Default Value No Read Only Shows ...

Страница 76: ...ue 86 0 F 30 0 C Range 75 to 122 F 24 to 50 C Ambient Low Temperature Alarm Ambient Low Default Value 40 0 F 4 5 C Range 32 to 45 F 0 to 7 C Refrig High Temperature Alarm Refrigerator High only present if a refrigeration sensor is installed Default Value 40 0 F 4 5 C Range 32 to 50 F 0 to 10 C Refrig Low Temperature Alarm Refrigerator Low only present if a Refrigeration sensor is installed Default...

Страница 77: ...ry Off Choices On or Off Water Leak Water Leak Sensor Status Default Value Off Read Only Shows if any water sensor paired device has detected a water leak On or no leak de tected in any of the water sensor paired devices Off Choices On or Off Low Temp Low Temperature Alarm Default Value Off Read Only Shows if any temperature sensor paired device has detected a low temperature On or no low temperat...

Страница 78: ...lt Value Idle Read Only Running LUA script active Halted LUA script stopped and not active Idle LUA script is running but not currently performing any actions Waiting LUA script running and waiting for a response Uploading LUA script currently unloading from the Room Controller Loading LUA script currently loading to the Room Controller Display Readings Idle Loading Running Waiting Halted Unloadin...

Страница 79: ...ter H AV226 BACnet Analog Object Value Properties Default Value 0 The value of this parameter depends on what is assigned to it from a BAS or LUA script Parameter I AV227 BACnet Analog Object Value Properties Default Value 0 The value of this parameter depends on what is assigned to it from a BAS or LUA script Parameter J AV228 BACnet Analog Object Value Properties Default Value 0 The value of thi...

Страница 80: ...New Issue UM_MultiSITE_RoomController_VAV_MS8250_09_20 LG Electronics U S A Inc Air Conditioning Technologies 4300 North Point Parkway Alpharetta Georgia 30022 www lghvac com ...