1/2 Setpoints
Occ. cool
Standby cool
Unocc. cool
78.0 °F
74.5 °F
71.5 °F
69.0 °F
62.0 °F
80.0 °F
Occ. heat
Standby heat
Unocc. heat
Table 28: Setpoints 1 / 2 Parameter Details.
Configuration Parameters Default Value
Significance and Adjustments
Unocc. Cool (Unoccupied Cool Setpoint)
Default Value: 80°F (27°C)
Cooling Temperature setpoint used by the Room Controller when in Unoccupied mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Standby Cool (Standby Cool Setpoint)
Default Value: 78°F (25.5°C)
Cooling Temperature setpoint used by the Room Controller when in Standby mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Occ. Cool (Occupied Cool Setpoint)
Default Value: 75.0°F (24.0°C)
Cooling Temperature setpoint used by the Room Controller when in Occupied or Override
mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Occ. Heat (Occupied Heat Setpoint)
Default Value: 72.0°F (22.0°C)
Heating Temperature setpoint used by the Room Controller when in Occupied mode.
Range: 40 to 90°F (4.5 to 32.0°C)
Standby Heat (Standby Heating Setpoint)
Default Value: 69.0°F (20.5°C)
Heating Temperature setpoint used by the Room Controller when in Standby mode.
Range: 40 to 90°F (4.5 to 32.0°C)
Unocc. Heat (Unoccupied Heating Setpoint)
Default Value: 62.0°F (17°C)
Heating Temperature setpoint used by the Room Controller when in Unoccupied or Over-
ride mode.
Range: 40 to 90°F (4.5 to 32.0°C)
SETPOINTS SCREENS
Setpoints 1 / 2
Setpoints 1 / 2
Figure 35: Setpoints 1 / 2 Display.