3/9 Configuration
Reheat config.
Duct.+base
Duct heater
Floating
Float. heat time
1.5
OAT duct lock
83.0 °F
Baseboard
Relay
OAT base lock
30.5 °F
Configuration Parameters Default Value
Significance and Adjustments
Reheat Config. (Reheat Configuration)
Default Value: None
Reheat configuration for the zone, using the duct, baseboard or both.
Choices: None, Duct only, Base only, Duct+base, Base+duct.
Duct Heater (Duct Heater Control)
Default Value: On/Off
Displayed when Duct only, Duct+base or Base+duct is selected.
Floating is available when Fan type is not Par./Ser. ECM.
Choices: On/Off, PWM Vac, Valve NC, Valve NO, 0-10V DA, 0-10V RA, 2-10V DA, 2-10V
RA, Floating.
Float. Heat Time (Floating Heat Time)
Default Value: 1.5 min
Displayed when Floating Duct heater is selected.
Range: 0.5 min to 9.0 min, using 0.5 min increments.
OAT Duct Lock)
Default Value: 60.0°F (15.5°C)
Outside air temperature above which duct reheat will be disabled.
Displayed when Duct only, Duct+base or Base+duct is selected.
Range: 30.0°F (-1.0°C) to 90.0°F (32.0°C) using 0.5°F (0.5°C) increments.
Baseboard (Baseboard Control)
Default Value: Relay
Output type used for baseboard control.
Displayed when Base only, Duct+base or Base+duct is selected.
Choices: Relay, PWM Vac, Valve NC, Valve NO.
OAT Base Lock
Default Value: 60.0°F (15.5°C)
Outside air temperature above which baseboard reheat will be disabled.
Displayed when Base only, Duct+base or Base+duct is selected.
Range: 30.0°F (-1.0°C) to 90.0°F (32.0°C) using 0.5°F (0.5°C) increments.
Configuration 3 / 9
CONFIGURATION SCREENS
Configuration 3 / 9
Figure 24:
Configuration 3 / 9 Display.
Table 16:
Configuration 3 / 9 Parameter Details.