Refrigerant piping system
Calculation of amount of refrigerant
The calculation of the additional charge should take account of the diameter and length of the pipe.
Additional charge (kg)
Product Charge(kg)
=
+
+
+
+
+
+
+
=
+
Total liquid pipe (m): Ø22.2mm
x 0.354(kg/m)
Total liquid pipe (m): Ø25.4 mm
x 0.480(kg/m)
x 0.266(kg/m)
x 0.173(kg/m)
x 0.118(kg/m)
x 0.061(kg/m)
x 0.022(kg/m)
Total liquid pipe (m): Ø19.05mm
Total liquid pipe (m): Ø15.88mm
Total liquid pipe (m): Ø12.7mm
Total liquid pipe (m): Ø9.52mm
Total liquid pipe (m): Ø6.35mm
CF(kg)
(Correction Factor)
Total amount(kg)
If a negative result is obtained from
the calculation, no refrigerant needs
to be added.
A
A
B
B
CAUTION
Outside unit
Header branch
Indoor
unit
Ex) 10HP
Additional Charge = A x 0.061 + B x 0.061 + C x 0.061
+ D x 0.061 + E x 0.022 + CF
= 50 x 0.061 + 10 x 0.061 + 10 x 0.061
+ 10 x 0.061 + 10 x 0.022 + 0(CF)
=
5.1kg
A : Ø9.52, 50m
B : Ø9.52, 10m
C : Ø9.52, 10m
D : Ø9.52, 10m
E : Ø6.35, 10m
Attach the additional refrigerant table of IDU.