48
Outside Unit
Dip switch setting
Mode Function
Option
Value
Action
Remarks
Content
Display1
Content
Display2
Content
Display3
Content Display4 Implement Display5
Installation
Cool & Heat Selec-
tor
OFF op1~op2
Selected the
option
- -
Change the
set value
Blank
Save in
EEPROM
Geothermal mode
setting
OFF
ON
Selected the
option
- -
Change the
set value
Blank
Save in
EEPROM
Sol. Valve
200 V output
OFF
ON
Selected the
option
- -
Change the
set value
Blank
Save in
EEPROM
Variable water flow
control
OFF
ON
Selected the
option
- -
Change the
set value
Blank
Save in
EEPROM
ODU address
-
-
0~255
Set the
value
Change the
set value
Blank
Save in
EEPROM
Target pressure ad-
justing
OFF op1~op3
Selected the
option
- -
Change the
set value
Blank
Save in
EEPROM
Use Sump Heater
OFF
ON
Selected the
option
- -
Change the
set value
Blank
Save in
EEPROM
IDU capacity
adjusting
OFF
ON
Selected the
option
-
-
Change the
set value
Blank
Save in
EEPROM
* Functions save in EEPROM will be kept continuously, though the system power was reset.
To cancel the function you need to set OFF.
DIP-SW01 7 - Segment
SW01C (
̻
: confirm)
SW02C (
ඔ
: backward)
SW03C (
ඖ
: forward)
SW04C ( : cancel)
SW01D (reset)
Setting the function
Select the mode/function/option/value using ‘
▶
’, ‘
◀
’ Button and confirm that using the ‘
●
’ button after dip switch
No.5 is turned on.
CAUTION
• It is only executed when all indoor units are off
.
Electrical Wiring
MFL67705803 2018. 9. 17. 오오 12:58 Page 48