Refrigerant piping system
Installation Manual
29
ENGLISH
- The pipes between the outside units must maintain horizontal levelness or give an inclination to prevent a back
flow toward the slave outside unit. Otherwise, the unit may not operate properly.
Toward indoor unit
Toward indoor unit
Pipe inclination (2 or more)
Toward indoor unit
Toward indoor unit
Toward indoor unit
Toward indoor unit
(Example 1)
(Example 2)
(Example 3)
Examples of Wrong Pipe Connections
• If outside units are located at different level, oil trap must be installed after each Y branch.
• Oil trap should be located at same level of Y branch. (Heat Pump : High Pressure Vapor / Heat Recovery : High Pressure
Vapor & Low Pressure Vapor)
Level
Level
Level
Level
• If pipe is higher than outside unit, oil trap must be installed after each Y branch
• Oil trap should be located at same level of Y branch. (Heat Pump : High Pressure Vapor / Heat Recovery : High Pressure
Vapor & Low Pressure Vapor)