Installation Manual
45
ENGLISH
Electrical Wiring
1. 60Hz
u
Example Connection of Power and Communication Cables
n
Single Outside Unit - 3Ø, 380-415 V
R S T
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Outside Unit]
[Indoor Units]
3 Phase 4 Wires
Power supply
50Hz 380-415 V
Power supply
1 Phase 50Hz
220-240 V
(Main Switch)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
The GND terminal at the main PCB is
a ‘-’ terminal for day contact, it is not the
point to make ground connection.
Between Indoor and Master Outside unit
Master
Outside Unit
3(A) 4(B)
SODU B SODU A
IDU B
IDU A
INT B
INT A
3(A) 4(B)
3(A) 4(B)
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage.
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install a main electrical protection to interrupt power to all equipment of the system because this system consists of
the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while
the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
WARNING
Frequency
Voltage range(V)
Outdoor
Indoor
60Hz
460V
220V
MFL67705803 2018. 9. 17. 오오 12:58 Page 45