Refrigerant piping system
30
Outside Unit
- When connecting the pipes between the outside units, the accumulation of oil in the slave outside unit should be
avoided. Otherwise, the unit may not operate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
h
Toward indoor unit
(Example 2)
- Apply Oil Trap as shown below when the length of the pipe between the outside units is more than 2m. Otherwise,
the unit may not operate properly.
Toward indoor unit
Toward indoor unit
2 m(6.6 ft) or less
2 m(6.6 ft) or less
2 m(6.6 ft) or longer
0.2 m(0.66 ft) or longer
Oil Trap
(Example 2)
(Example 1)