98
Indoor Unit
Operation Details
■
Protection of the evaporator pipe from frosting
If the te
mperature of the indoor coil is below -2°C after 7 minutes from starting the compressor,
the compressor and the outdoor fan is stopped, and then after 3 minute delay of the compressor
and the temperature of the indoor coil is over 7°C, the compressor and the outdoor fan is reoper-
ated.
Indoor fa
n operates at low speed (comp. OFF) or at selected speed (comp. ON)
■
Inlet grille open
Once the inlet grille is opened during operation of the unit, the unit automatically stops operation and the lamps
will be turned-off. But memorized functions are still available.
When the inlet grille is closed again, the unit become waiting state for operation. From then, the unit can be
operated by forced operation button or Start/Stop button of remote controller.
■
Test Operation
• When pressing forced operation switch about 3 seconds, the unit operates in cooling mode at high speed
fan regardless of room temperature and resets in 18 min.
• During test operation, if remote controller signal is received, the unit operates as remote controller sets.
■
Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance is in operation, the mode
before the power failure is kept on the memory and the appliance should operate automatically in the
mode kept in the memory.
• Operation Mode that is kept on the memory
- State of Operation ON/OFF
- Operation Mode/Setting Temperature /Selected airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer(unit of hour)
• If no input by the remote controller or no switching of the slide switch within 7 hours after the appliance
operates by the Auto Restarting operation, the appliance is forced to stop at the moment of 7 hours
elapse.
Содержание multi V PLUS
Страница 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Страница 74: ...74 Indoor Unit ...
Страница 86: ...86 Indoor Unit ...
Страница 142: ...142 Indoor Unit ...
Страница 160: ...160 Indoor Unit ...
Страница 179: ...Service Manual 179 Outdoor unit ...
Страница 232: ...232 Outdoor Unit Wiring Diagrams 5 Wiring Diagrams 5 1 50Hz 380V Main Outdoor Unit 5HP 6HP 8HP ...
Страница 235: ...Service Manual 235 Wiring Diagrams 380V AC 60Hz 3Ø 5 4 60Hz 380V Main Outdoor Unit 5HP 6HP 8HP ...
Страница 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Страница 245: ...Service Manual 245 Trouble shooting guide ...
Страница 296: ...296 Trouble Shooting Guide ...
Страница 297: ...Service Manual 297 Appendix ...
Страница 303: ...Service Manual 303 Exploded View Replacement Parts List ...