132
Indoor Unit
Operation Details
3) Fuzzy Operation for Heating
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above
the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp
➲
Setting Temp
Compressor OFF Temp
➲
Setting Temp + 3°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
20°C
≤
Intake Air Temp
➲
Intake Air Temp + 0.5°C
Intake Air Temp<20°C
➲
20°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature.
■
Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow
speed selection key on the remote control.
■
On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
■
Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.
■
Off-Timer
↔
On-Timer Operation
• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation
is carried out according to the set time.
■
Sleep Timer Operation
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in
appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C. After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.
Содержание multi V PLUS
Страница 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Страница 74: ...74 Indoor Unit ...
Страница 86: ...86 Indoor Unit ...
Страница 142: ...142 Indoor Unit ...
Страница 160: ...160 Indoor Unit ...
Страница 179: ...Service Manual 179 Outdoor unit ...
Страница 232: ...232 Outdoor Unit Wiring Diagrams 5 Wiring Diagrams 5 1 50Hz 380V Main Outdoor Unit 5HP 6HP 8HP ...
Страница 235: ...Service Manual 235 Wiring Diagrams 380V AC 60Hz 3Ø 5 4 60Hz 380V Main Outdoor Unit 5HP 6HP 8HP ...
Страница 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Страница 245: ...Service Manual 245 Trouble shooting guide ...
Страница 296: ...296 Trouble Shooting Guide ...
Страница 297: ...Service Manual 297 Appendix ...
Страница 303: ...Service Manual 303 Exploded View Replacement Parts List ...