Service Manual 171
Operation Details
■
Chaos Swing Mode
• By the Chaos Swing key input, the louvers vane automatically operate with the Chaos Swing or they are fixed
to the desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
■
Jet Cool Mode Operation (H/P Model)
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• During the JET HEAT function at any moment, the A/C starts to blow the hot air with side louvers closed at
extremely high speed for 60 minutes setting the room temp. automatically to 30°C.
■
Forced Operation
• Operation procedures when the remote control can't be used.
• The operation will be started if the power button is pressed.
• If you want to stop operation, re-press the button.
• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times
to indicate the forced operation.
■
Test operation
•
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem-
perature and resets in 18±1 minutes.
•
During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, open the front panel upward and Press the power button let it be pressed
for about 3 seconds.
•
If you want to stop the operation, re-press the button.
Room temperature
≥
24°C
21°C
≤
Room temperature < 24°C
Room temperature < 21°C
Operating mode
Cooling
Healthy Dehumidification
Heating
Indoor FAN Speed
High
High
High
Setting Temperature
22°C
23°C
24°C
CLOSED
OPEN
< Cooling Mode >
7
°
CLOSED
OPEN
< Heating Mode >
7
°
Содержание multi V PLUS
Страница 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Страница 74: ...74 Indoor Unit ...
Страница 86: ...86 Indoor Unit ...
Страница 142: ...142 Indoor Unit ...
Страница 160: ...160 Indoor Unit ...
Страница 179: ...Service Manual 179 Outdoor unit ...
Страница 232: ...232 Outdoor Unit Wiring Diagrams 5 Wiring Diagrams 5 1 50Hz 380V Main Outdoor Unit 5HP 6HP 8HP ...
Страница 235: ...Service Manual 235 Wiring Diagrams 380V AC 60Hz 3Ø 5 4 60Hz 380V Main Outdoor Unit 5HP 6HP 8HP ...
Страница 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Страница 245: ...Service Manual 245 Trouble shooting guide ...
Страница 296: ...296 Trouble Shooting Guide ...
Страница 297: ...Service Manual 297 Appendix ...
Страница 303: ...Service Manual 303 Exploded View Replacement Parts List ...