Service Manual 211
Function
2.4 Stopping operation
2.4.1 Stopping operation on cooling mode
2.4.2 Stopping operation on heating mode
Inv Compressor
Fan
Main LEV
4 way valve
Subcooling LEV
0 Hz
0 Hz
Full open
On
Full open
Operation
Component
After 15 min from stop, min.
After 15 min from stop, off
After 15 min from stop, min.
Note
Sub unit ’s
compressor
Off
Hot gas bypass
On
After 15 min from stop, Off
Inv Compressor
Fan
Main LEV
4 way valve
Subcooling LEV
0 Hz
0 Hz
Full open
Off
Full open
Operation
Component
After 15 min from stop, min.
Off
-
-
-
-
-
-
After 15 min from stop, min.
Note
Sub unit ’s
compressor
Off
Hot gas bypass
On
After 15 min from stop, Off