266
Trouble Shooting Guide
Self-diagnosis function
No
Check or replace
the indoor unit PCB
Check and replace
the indoor unit PCB.
Change the operation mode of
indoor unit to the same operation
mode of outdoor unit
Yes
Yes
Fault diagnosis and Trouble shooting guide
07
Failure Checking Method
Failure Checking Method
Different
operation
mode
between
indoor
units
Where operating in different
operation mode from previously
operated indoor unit
This error occurs if an indoor unit which is off
state is to operate in heating mode when one or
more indoor units are operated in cooling mode
and vice versa.
09
Indoor
unit
EEPROM
error
Problems occur at EEPROM
within the indoor unit
°
Øs main
PCB assembly
• Occurrence of poor communication between
MICOM and EEPROM on the indoor unit main
PCB assembly.
• Occurrence when no serial No. data exist within
EEPROM.
Are both operation mode of the
indoor unit and that of the outdoor
unit same?
Change so that operation mode of
both the indoor unit and the outdoor
unit becomes same
Error
Item
Error Display
No.
Major Error Occurrence Cause
Meaning
Error
Item
Error Display
No.
Major Error Occurrence Cause
Meaning
Содержание multi V PLUS
Страница 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Страница 74: ...74 Indoor Unit ...
Страница 86: ...86 Indoor Unit ...
Страница 142: ...142 Indoor Unit ...
Страница 160: ...160 Indoor Unit ...
Страница 179: ...Service Manual 179 Outdoor unit ...
Страница 232: ...232 Outdoor Unit Wiring Diagrams 5 Wiring Diagrams 5 1 50Hz 380V Main Outdoor Unit 5HP 6HP 8HP ...
Страница 235: ...Service Manual 235 Wiring Diagrams 380V AC 60Hz 3Ø 5 4 60Hz 380V Main Outdoor Unit 5HP 6HP 8HP ...
Страница 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Страница 245: ...Service Manual 245 Trouble shooting guide ...
Страница 296: ...296 Trouble Shooting Guide ...
Страница 297: ...Service Manual 297 Appendix ...
Страница 303: ...Service Manual 303 Exploded View Replacement Parts List ...