48
Indoor Unit
Operation detail
Intake Air temperature
Setting Temperature .+3°C
(Compressor OFF)
Setting Temperature
(Compressor ON)
INDOOR FAN
Low
OFF Low
Low
OFF
■
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Hot Start
Low
Selecting
Fan Speed
minimum 3min
Selecting fan
speed
minimum
10sec.
1min
A
A
minimum
1min.
minimum
10sec.
B
■
Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
The operation diagram is as following.
PIPING
TEMPERATURE
1min
COMPRESSOR
INDOOR FAN
OFF
LOW
Selected Fan
ON
22
°
C
25
°
C
• A point;
While the indoor Heat-Exchanger temperature is higher than 40°C fan operates at low speed,
when it becomes lower than 40˚C fan stops.
• B point;
When the indoor Heat-Exchanger temperature is higher than 31°C, fan operates at selected fan
speed, when it becomes lower than 31°C, the fan operates at low speed for 10sec, after 10sec, it
operates at selected fan speed.
Содержание multi V PLUS
Страница 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Страница 74: ...74 Indoor Unit ...
Страница 86: ...86 Indoor Unit ...
Страница 142: ...142 Indoor Unit ...
Страница 160: ...160 Indoor Unit ...
Страница 179: ...Service Manual 179 Outdoor unit ...
Страница 232: ...232 Outdoor Unit Wiring Diagrams 5 Wiring Diagrams 5 1 50Hz 380V Main Outdoor Unit 5HP 6HP 8HP ...
Страница 235: ...Service Manual 235 Wiring Diagrams 380V AC 60Hz 3Ø 5 4 60Hz 380V Main Outdoor Unit 5HP 6HP 8HP ...
Страница 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Страница 245: ...Service Manual 245 Trouble shooting guide ...
Страница 296: ...296 Trouble Shooting Guide ...
Страница 297: ...Service Manual 297 Appendix ...
Страница 303: ...Service Manual 303 Exploded View Replacement Parts List ...