Installation
Installation Manual
9
3) Piping length and the elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
CAUTION:
• Rated performance for refrigerant line length of: 5.0m or 7.5m
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.
Model
*Additional
refrigerant
(g/m)
Pipe Size
mm(inch)
Length A(m)
Elevation B(m)
Gas
Liquid
Standard
Max.
Standard
Max.
LT-H182QLE1
12.70(1/2”)
6.35(1/4”)
7.5
30
5
20
30
LT-H242PLE1
15.88(5/8”)
6.35(1/4”)
7.5
30
5
20
35
LT-H302NLE1
15.88(5/8")
6.35(1/4")
5.0
50
5
30
25
LT-H362NLE1
15.88(5/8")
6.35(1/4")
5.0
50
5
30
40
LT-H482MLE1
19.05(3/4")
9.52(3/8")
7.5
50
5
30
45
LT-H602MLE1
19.05(3/4")
9.52(3/8")
5.0
50
5
30
50
LT-C182QLE1
12.70(1/2”)
6.35(1/4”)
7.5
30
5
20
30
LT-C242PLE1
15.88(5/8”)
6.35(1/4”)
7.5
30
5
20
35
LT-C302NLE1
15.88(5/8")
6.35(1/4")
5.0
50
5
30
25
LT-C362NLE1
15.88(5/8")
6.35(1/4")
5.0
50
5
30
40
LT-C482MLE1
19.05(3/4")
9.52(3/8")
7.5
50
5
30
45
LT-C602MLE1
19.05(3/4")
9.52(3/8")
5.0
50
5
30
50