Installation Manual
29
Installation
2) General Ventilation product
j
Some contents may not be displayed depending on the product function
No.
Function
Code
Value
1
Test Run
01
01 : Test Run Setup
2
02
00~FF : Address of Central Control
3
SA(Supply Air) ESP
03
<ESP level>
<ESP value>
<Example>
4
EA(Exhaust Air) ESP
04
01 : Low
0~255
02 : High
03 : Super High
5
Product Direction
05
01 : Normal
02 : Opposite
6
Quick Refresh Priority
06
01 : Supply Air First
02 : Exhaust Air First
7
Master Setting
07
00 : Slave
01 : Master
8
Override Setting
08
00 : Slave
01 : Master
9
Dry Contact
09
00 : Auto-Off
01 : Auto-On
10
Release Of 3 Minute Delay
10
01 : Set
11
Zone State
11
01 : Variable
02 : Fixed
12
Humidification for Singular
13
00 : Not in Use
Ventilation
01 : Use
13
Humidification for Heat Mode
14
00 : Automatic
Ventilation
01 : Manual
Address Setting
Function Code
ESP value
ESP step