Ceiling Concealed Duct
Inverter
50Hz/R410A
_
31
Part 2 Product Data
Note: 1. The above table shows the conrrelation of Extemal Static Pressure & Air Flow.
2. When installing, the value of motor step needs to be set according to E.S.P. of the table 1.
Table 2
9. External Static Pressure & Air Flow
Static Pressure(Pa)
50
60
70
80
100
Model Name
Step
Setting Value
l/s
l/s
l/s
l/s
B30AWYN7G5A
High
Med
Low
B36AWYN7G5A
High
Med
Low
Static Pressure(Pa)
60
80
100
120
140
160
180
Model Name
Step
Setting Value
l/s
l/s
l/s
l/s
l/s
l/s
l/s
B42AWYN7G5A
High
88
852
745
573
346
-
-
-
Med
81
761
675
433
-
-
-
-
Low
77
657
554
-
-
-
-
-
B55AWYN7G5A
High
100
1,168
1,043
914
795
659
487
355
Med
92
1,007
867
719
551
397
-
-
Low
86
890
694
572
401
-
-
-
70
630
533
349
-
-
67
544
449
267
-
-
64
476
307
-
-
-
74
731
648
484
-
-
71
648
564
346
-
-
67
544
449
267
-
-