Ceiling Concealed Duct
Inverter
50Hz/R410A
_
3
Part 2 Product Data
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length: - Interconnecting Piping Length 5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without notic for purpose of improvement.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
2. Specifications
2.1 Indoor Unit
Model Name
B30AWYN7G5A
B36AWYN7G5A
Power Supply
V, Ø, Hz
Power Input
kW
Running Current
A
Dimensions
Body
W x H x D
mm
W x H x D
inch
Net Weight
Body
kg (lbs)
Heat
Exchanger
(Row x Column x Fins per inch) x No.
-
Face Area
m
2
(ft
2
)
Fan
Type
-
Air
Flow
Rate
High-static
Mode
(Factory
Set)
H / M / L
m
3
/min
H / M / L
l/s
External Static
Pressure
Pa (mmAq)
External Static Pressure
Min.~Max. Pa (mmAq)
Fan Motor
Type
-
Output
W x No.
Dehumidification Rate
l
/ h (pts/h)
Sound Pressure Level
H / M / L
dB(A)
Piping
Connections
Liquid
mm(inch)
Gas
mm(inch)
Drain (O.D. / I.D.)
mm
Safety Devices
-
-
Power and Communication Cable (included Earth)
No. x mm
2
(AWG)
220-240, 1, 50
220-240, 1, 50
0.27
0.37
1.2
1.6
1,320 × 400 × 534
1,320 × 400 × 534
51-31/32 × 15-3/4 × 21-1/32
51-31/32 × 15-3/4 × 21-1/32
47.0 (103.6)
47.0 (103.6)
(2 x 16 x 19) x 1
(2 x 16 x 19) x 1
0.39 (4.2)
0.39 (4.2)
Sirocco Fan
Sirocco Fan
32.0 / 26.0 / 20.0
42.0 / 36.0 / 28.0
533 / 433 / 333
700 / 600 / 467
60 (6.12)
60 (6.12)
60~200 (6.1~20.4)
60~200 (6.1~20.4)
BLDC
BLDC
350 x 1
350 x 1
0.97 (2.0)
2.0 (4.3)
44 / 43 / 42
45 / 44 / 43
Ø 9.52 (3/8)
Ø 9.52 (3/8)
Ø 15.88 (5/8)
Ø 15.88 (5/8)
Ø 32 / 25
Ø 32 / 25
Fuse
Fuse
-
-
4C x 1.0 (18)
4C x 1.0 (18)
Содержание B30AWYN7G5A
Страница 1: ...Ceiling Concealed Duct Inverter 50Hz R410A 5CSB0 02B Replace 5CSB0 02A P No MFL49500009 ...
Страница 4: ...Part 1 General information 1 Models List 2 Nomenclature 3 Features Benefits Ceiling Concealed Duct ...
Страница 52: ...Part 3 Design and installation 1 Installation Ceiling Concealed Duct ...
Страница 75: ...Part 4 Accessories 1 Function of Remote Control 2 Central Control Devices Ceiling Concealed Duct ...