Ceiling Concealed Duct
Inverter
50Hz/R410A
_
35
Part 2 Product Data
How to Set E.S.P?
E.S.P function is setting the volume of each air flow. It is for the convenience of installation.
It is recommended that you should not use this function while using the wireless remote controller.
1. Press
button to appear
button on the
screen. mode.
2. Press the
button for
3secs.
3. Press the
button.
4. Set the volume of each air flow
( LOW’MID’HI) by using the
button.
Press the
button to select the air flow.
(The value of E.S.P could be adjusted from 1 to
255.) (The figure on the left shows when the
strong wind’s E.S.P value has been set to 255.)
5. If you press the
button, the E.S.P value will
be set.
100 unit
10 unit
CAUTION:
If you set E.S.P incorrectly, the air conditioner may malfunction.
This setting must be carried out by authorized personnel only.
11. E.S.P.(External Static Pressure) setting for