Ceiling Concealed Duct
Inverter 50Hz/R410A
_
21
Part 2 Product Data
n
Remote Temperature Sensor(PQRSTA0)
- After deciding where the remote temperature sensor is installed,
decide the location and height of the fixing screws.
(Interval between the screws : 60mm).
- After removing the control box cover of the indoor unit,
remove the room temperature sensor in CN-ROOM of the main PCB.
- Insert the connector of remote sensor wire into CN-ROOM.
- Using the DC line hole when connecting the wire to Indoor PCB.
- For using the two thermistor fuction, the remote sensor should be installed
from the wired remote controller as far as possible.
- Refer to damper remote sensor manual for detailed installation metheod.
Fixing
screws
60mm
Remote sensor
Connecting wire
CN-ROOM
1. Installation