8. Installation
37
MULTI/SINGLE
Indoor unit
Ceiling Mounted cassette 4-way
8.5 Installation of Decoration Panel
CAUTION
•
Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
8.6 Indoor Unit Drain Piping
8.6.1 Drain piping of indoor unit with drain pump
• Drain piping must have down-slope (1/50 to 1/100). Be sure not to provide up-and-down slope to prevent
reversal flow.
• During drain piping connection, be careful not to exert force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the indoor unit is 32 mm (1-1/4 inch).
– Piping material: Use the Polyvinyl chloride pipe, 25 mm (1 inch) pipe fittings.
•
The decoration panel has its installation direction.
•
Before installing the decoration panel, always remove the paper template.
Good case
Bad case
Fit the insulator (this part) and
be careful for cool air leakage
Decorative panel
Air conditioner
unit
Ceiling
board
Good example
Cool air leakage
(no good)
Decorative panel
Air conditioner
unit
Ceiling
board
Bad example
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
※
According to type of indoor unit, external appearance could be different.
1/50~1/100 slope
Hanger
distance
Hanger bracket
Max 700mm
Flexible drain hose
Insulation
Metal
clamp
Max 300mm
1~15m
※
According to type of indoor unit, external appearance could be different.
Содержание AM07BP NSJ
Страница 1: ...Indoor unit R32 Heat Pump 50 60Hz 0CTI5 02A Replaces 0CTI5 01C P No MFL67502513 ...
Страница 3: ...General information MULTI SINGLE Indoor unit 1 Model Line Up 2 External Appearance 3 Nomenclature ...
Страница 33: ...22 MULTI SINGLE Indoor unit Wall Mounted Unit 5 Wiring Diagrams Deluxe Model AMNW07GSJL0 DM07RP NSJ ...
Страница 140: ...MULTI SINGLE Indoor unit 3 Dimensions 14 Ceiling Mounted cassette 4 way ZTNW18GQLA0 CT18R NQ0 ...
Страница 141: ...3 Dimensions 15 MULTI SINGLE Indoor unit Ceiling Mounted cassette 4 way ZTNW24GPLA0 CT24R NP0 ...