16
MULTI/SINGLE
Indoor unit
Ceiling concealed duct - Middle static pressure
6. External Static Pressure & Air Flow
̰
How to Set E.S.P. on the remote controller?
This is the function that decides the strength of the wind for each wind level and because this function is to make
the installation easier.
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
• When setting ESP value on the product without very weak wind or power wind function, it may not work.
• Please be careful not to change the ESP value for each fan step.
• It does not work to setup ESP value for very low/power step for some products.
• ESP value is available for specific range belongs to the product.
If entering into ESP setup mode by using
button, it indicates as the picture
below.
2
Select ESP fan step by
pressing button.
(01: very low, 02: low, 03:
medium, 04: high, 05:
very high)
3
Move to ESP value setting by pressing
button.
(It is 000 when delivering
from the warehouse.)
4
Press button to setup ESP value.
(It is possible to setup ESP
value from 1 to 255, and 1 is
the smallest and 255 is the
biggest.)
5
If pressing button long for 3
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
1
Function Code
ESP value
ESP step
Press button to save.
7
Select ESP fan step again by using
button and setup ESP value, as No. 4
and 5, that corresponds each wind flow
6
Press button to exit.
After setup, it automatically gets out of
setup mode if there is no button input
for 25 seconds.
When exiting without pressing set
button, the manipulated value is not
reflected.
8
Function code,
ESP code
ESP value
Содержание AM07BP NSJ
Страница 1: ...Indoor unit R32 Heat Pump 50 60Hz 0CTI5 02A Replaces 0CTI5 01C P No MFL67502513 ...
Страница 3: ...General information MULTI SINGLE Indoor unit 1 Model Line Up 2 External Appearance 3 Nomenclature ...
Страница 33: ...22 MULTI SINGLE Indoor unit Wall Mounted Unit 5 Wiring Diagrams Deluxe Model AMNW07GSJL0 DM07RP NSJ ...
Страница 140: ...MULTI SINGLE Indoor unit 3 Dimensions 14 Ceiling Mounted cassette 4 way ZTNW18GQLA0 CT18R NQ0 ...
Страница 141: ...3 Dimensions 15 MULTI SINGLE Indoor unit Ceiling Mounted cassette 4 way ZTNW24GPLA0 CT24R NP0 ...