MULTI/SINGLE
Indoor unit
7. Installation
14
Ceiling concealed duct - Low static pressure
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.
2. Avoid installing air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
CAUTION
• If the temperature rise above 30
or the humidity rise above RH 80%, the dew-protective kit should be equipped
or use additional insulation to the indoor unit body.
– "Dew Protective kit" is sold separately.
– Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least.
Chassis code
A [mm]
B [mm]
L1
800
800
L2
800
1,000
L3
800
1,200
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
Air conditioner or
Ducted air diffuser
Take enough
distance
※
According to type of indoor unit, external appearance
or installed structure could be different.
Inspection hole
(600 x 600)
Control box
600
600
(Unit: mm)
Top view
A(Min)
Ceiling
Service Space
A
B(Min)
H=20 or more
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
Side view
(unit: mm)
Содержание AM07BP NSJ
Страница 1: ...Indoor unit R32 Heat Pump 50 60Hz 0CTI5 02A Replaces 0CTI5 01C P No MFL67502513 ...
Страница 3: ...General information MULTI SINGLE Indoor unit 1 Model Line Up 2 External Appearance 3 Nomenclature ...
Страница 33: ...22 MULTI SINGLE Indoor unit Wall Mounted Unit 5 Wiring Diagrams Deluxe Model AMNW07GSJL0 DM07RP NSJ ...
Страница 140: ...MULTI SINGLE Indoor unit 3 Dimensions 14 Ceiling Mounted cassette 4 way ZTNW18GQLA0 CT18R NQ0 ...
Страница 141: ...3 Dimensions 15 MULTI SINGLE Indoor unit Ceiling Mounted cassette 4 way ZTNW24GPLA0 CT24R NP0 ...