- 81 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Trouble Shooting
Check the indoor
fan motor. (Fan is locked
by obstruction)
Is it normal ?
Check the connection
status between PCB
and fan motor
Check the DC Motor
signal
Is it normal ?
Yes
Yes
No
Remove obstruction
No
Correct connection Or re-soldering PCB
Is it normal ?
Repair or Change the PCB.
Yes
No
Change Indoor Motor
Check Flow Chart
67
BLDC motor
fan lock (Outdoor)
• Fan motor break down
• Fan motor & PCB poor
contact
• Obstruction to the fan
• Check the indoor fan motor.
• Check the connection status between
• PCB and fan motor.
Display
code
Title
Cause of error
Check point & Normal condition