Test Run
Is cold water discharged for
more than 3 minutes ?
START
Test operation for indoor unit
Operation mode change
to Heating mode
Operate the unit in cooling mode.
Does Test operation start?
Refer to part4, 6 Electric part
Yes
No
Yes
Refer to part4, 5 Cycle part
No
Is hot water discharged ?
After Hot Start
Yes
No
Is there any temperature
difference between intake and
discharged water?
Yes
No
Is the operating current
normal ?
Yes
Normal
Refer to Troubleshooting
Guide
No
* Check the load (In/Out Temp.)
* Check pipe length and amount of
refrigerant
* Check for abnormal sound in
outdoor unit (comp.,Fan, others )
2. Test Run Flow chart