- 38 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Control logic
7.1 Function
:These are controls of compressor, fan of outdoor unit, reversing valve, and EEV..
7.2 Starting to the defrosting operation
A) Defrost operation will be started when all the conditions below are matched simultaneously
Accumulation time of operation and the period after completion of defrost = 35min (Outdoor air temperature –3˚C)
B) Outdoor piping temperature is below than –6 (Option)˚C for starting defrosting operation.
7.3 Completion of defrost operation
Send signal of defrost completion in case of meeting one of the condition as below.
1. Defrosting time
≥
7 minutes
2. Piping temperature maintain 10 seconds (Option ) in condition of more than 12˚C (Option).
7.4 Defrosting Control Algorithm
7. Defrost Control
Satisfy
Defrost
Start
Condition
Satisfy
Defrost
End
Condition
Defrost
Start
Heating
Start
(Defrost flag clear)
Inverter
Comp.
Outdoor Fan
Hot gas bypass
Indoor Fan
Reversing Valve
OFF
ON
OFF
OFF
ON
OFF
Hot
start
1 2
3
4
5
6
7
8
9
(Option)
Bypass valve
OFF
OFF
ON
10
11
80 Hz
(Option)
Control
45 Hz
(Option)
ON
OFF
ON/OFF
Maximum flow
Setting flow
Fan ON when pipe temperature
above 25
°
C(option)
Baseline
Step C
Step D
Step E
ON
Defrost signal of indoor unit on/
Starting maximum defrosting
time count
Indoor defrost signal OFF
Outdoor EEV
Control
350 Pulse
(Option)