- 40 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Control logic
8.2 Starting control (210 sec)
1) Only 1 EEV will be operate as below and others are closed fully.
2) Starting control does not use the time when the system operate with partial load after (example) after finishing starting
control for 1 indoor unit, another indoor unit is ON additionally is operated with target opening of EEV.
3) The indoor units which are in the middle of starting control are continuing starting control with the opening of its
opening.
4) Urgent control by indoor piping temperature
1. EEV open 4 pulse with every 10 sec when the indoor piping temperature is below 2˚C
2. When the temperature reaches 4˚C, system return to the starting control pulse value.
0.7 x Target Pulse(Cooling)
0.8 x Target Pulse
Target step
Time
30sec
150sec
0.9 x Target Pulse
Target Pulse
Time(Option)
Full open
Starting EEV
opening
Comp starting
270 sec
300 sec
330 sec