- 70 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Trouble Shooting
Check the wire
connection.(U,V,W)
Is it normal ?
Is it normal ?
Yes
Yes
No
Correct
connection
No
Change
Compressor
Check the input power
Is it normal ?
Yes
No
Change
Compressor
Check Flow Chart
❊
Dc link voltage table
❊
Check TRANS1
❊
Check DC link voltage
Type
Non operating
Operating
1 Phase
AUUW126C
PSC
DC300V
±
10%
DC280V
±
10%
AUUW186C
PSC
DC300V
±
10%
DC280V
±
10%
AUUW246D
PFC
DC300V
±
10%
DC380V
±
10%
AUUW306D
PFC
DC300V
±
10%
DC380V
±
10%
AUUW366D
PFC
DC300V
±
10%
DC380V
±
10%
AUUW426D
PFC
DC300V
±
10%
DC380V
±
10%
AUUW486D
PFC
DC300V
±
10%
DC380V
±
10%
AUUW606D
PFC
DC300V
±
10%
DC380V
±
10%
3 Phase
AUUW368D
PSC
DC540V
±
10%
DC500V
±
10%
AUUW428D
PFC
DC540V
±
10%
DC680V
±
10%
AUUW488D
PFC
DC540V
±
10%
DC680V
±
10%
AUUW608D
PFC
DC540V
±
10%
DC680V
±
10%
Model
DC Link Voltage
V
CN_TRANS 1
23
28
DC Link
Low voltage.
DC Link
High voltage
• 1ph : DC link volt. is
140Vdc .
• 3ph : DC link volt. is
250Vdc .
• 1ph : DC link volt. is
140Vdc .
• 3ph : DC link volt. is
250Vdc .
• Check the power source.
• Check the components.
• Check the power source.
• Check the components.
Display
code
Title
Cause of error
Check point & Normal condition
→
→
→
→
Содержание AH-W096A0