- 21 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Features
3.2 Control Panel Setting
Summary
Common Setting
• Function Code 01
: Test Run
Test run should be performed when additional refrigerant charging is required. To charge the refrigerant, the prod-
uct must run in Cooling mode. Test run instantly makes the product working in Cooling mode for 18 minutes.
Note
: • If you press any kind of button during this mode, Test Run mode will be finished.
• After running 18 minutes under test run mode, system will automatically turn OFF.
• Function Code 02
: Disable 3 minute Delay
Factory use only.
• Function Code 03
: Remote Air Sensor Connection
If user connects remote air sensor to control the product by room air temperature, the connection information
should be notified to the product.
Note
: If remote air sensor is connected but this function code is not set correctly, the product can not be con-
trolled by room air temperature.
• Function Code 04
: Celsius/Fahrenheit Switching
Temperature is displayed in Celsius or Fahrenheit.
• Function Code 05
: Setting Temperature Selection
The product can be operated according to air temperature or leaving water temperature. The selection for setting
temperature as air temperature or leaving water temperature is determined.
Note
: Air temperature as setting temperature is ONLY available when Remote Air Sensor Connection is enabled
and Function Code 03 is set as 02.
• Function Code 06
: Auto Dry Contact
This function allows the Dry contact-indoor unit operate under Auto Run mode or Manual mode with remote con-
trol panel.
• Function Code 07
: Address Setting
When Central Controller is installed, address assigning is set by this function.
Example of Fuction Code Display
Function Code Value #1
Value #2