In order to ensure the above air flow rate through natural ventilation, overall section A openings must be present in
the battery premises, equal to:
A = 28 Q
where:
A = section of ventilation openings (cm
2
Q = Q = ventilation air flow rate (m
3
/h).
Surface A of the openings must be intended as "free", meaning net of any obstacles to the airflow (grids)
Note: immediately near a battery charging, even in the presence of the a
EN 50272-3 provide the existence of a hazardous area which, due to its features, must be classified, according to
Standard EN 60079-10, as area 1 (place where it is possible, during normal operation, that an explo
forms due to the presence of gas).
According to Standard EN 50272-3, distance d for drive batteries is equal to 0.5m.
The distance varies depending on the battery features and, therefore, in the presence of more types of batteries, it
must be identified for each of them.
According to Standard EN50272-2, distance d for stationary batteries is identified by the following formula:
With natural and/or artificial ventilation with adequate availability, we can consider, for the purposes of safety,
providing around area 1, a boundary area 2.
LEVANTE s.r.l.
Via dell’Economia 10 – 46035 Ostiglia MN Italia
Reg. of Comp. of MN no. 01730440201 Share Cap. fully paid-up €20,800.00 Economic and Administrative Index
No. 178082
Tel. +39 0386 801814 Fax. +39 0386 801955
e-mail: [email protected]
NEWBINGO 2017-operating and mainspare parts v.02072017
In order to ensure the above air flow rate through natural ventilation, overall section A openings must be present in
2
),
/h).
Surface A of the openings must be intended as "free", meaning net of any obstacles to the airflow (grids)
Note: immediately near a battery charging, even in the presence of the above ventilation, Standards EN 50272
3 provide the existence of a hazardous area which, due to its features, must be classified, according to
10, as area 1 (place where it is possible, during normal operation, that an explo
3, distance d for drive batteries is equal to 0.5m.
The distance varies depending on the battery features and, therefore, in the presence of more types of batteries, it
2, distance d for stationary batteries is identified by the following formula:
With natural and/or artificial ventilation with adequate availability, we can consider, for the purposes of safety,
providing around area 1, a boundary area 2.
€20,800.00 Economic and Administrative Index
22
In order to ensure the above air flow rate through natural ventilation, overall section A openings must be present in
Surface A of the openings must be intended as "free", meaning net of any obstacles to the airflow (grids)
bove ventilation, Standards EN 50272-2 and
3 provide the existence of a hazardous area which, due to its features, must be classified, according to
10, as area 1 (place where it is possible, during normal operation, that an explosive atmosphere
The distance varies depending on the battery features and, therefore, in the presence of more types of batteries, it
2, distance d for stationary batteries is identified by the following formula:
With natural and/or artificial ventilation with adequate availability, we can consider, for the purposes of safety,