Electrical connection
Leuze electronic GmbH + Co. KG
ELC 100
24
6
Electrical connection
WARNING
Faulty electrical connection or improper function selection may result in serious injury!
Ä
Only allow qualified persons (Necessary competencies) to perform the electrical connection.
Ä
Make certain that the safety sensor is protected against overcurrent.
Ä
For access guarding, activate the start/restart interlock and make certain that it cannot be
unlocked from within the danger zone.
Ä
Ä
Select the safety-relevant functions for the safety sensor (see chapter 3.1 "Structure and
function").
Ä
Always loop both safety-related switching outputs OSSD1 and OSSD2 into the work circuit
of the machine.
Ä
Signal outputs must not be used for switching safety-relevant signals.
NOTICE
SELV/PELV!
Ä
Acc. to IEC/EN 60204-1, the external power supply must demonstrate the ability to bridge
short-term mains failures of up to 20 ms. The power supply unit must ensure safe mains
separation (SELV/PELV) and a current reserve of at least 2 A.
NOTICE
Laying cables!
Ä
Lay all connection cables and signal lines within the electrical installation space or perma-
nently in cable ducts.
Ä
Lay the cables and lines so that they are protected against external damages.
Ä
For further information: see ISO/EN ISO 13849-2, Table D.4.