Configuring the safety sensor
Leuze electronic
RSL 410
71
Figure 9.4: Confirmation: safety configuration downloaded
The software has saved the configuration project in the safety sensor.
9.7
Selecting access level
Using the device manager (DTM) you can change the access level of the user, if necessary see
chapter 5.1 "Authorization concept of safety sensor".
Click in the DTM menu bar on the [Change access level] button (
).
The Change access level dialog box opens.
In the Authorization list, select the item
Engineer
,
Expert
or
Observer
and enter the default password or
the password defined for the individual user (see chapter 4.5.6 "SETTINGS").
• Default password for
Engineer
: safety
• Default password for
Expert
: comdiag
Confirm with [OK].
9.8
Reset safety configuration
The device manager (DTM) can be used to reset the safety configuration to the default configuration (one
protective function, no restart).
In the DTM menu bar, click the [Reset safety configuration] button.
Users with the access level
Engineer
can additionally transfer the changed safety configuration to the
safety sensor (see chapter 9.6 "Transferring configuration project to safety sensor").
The safety-related switching outputs will already have switched on if all conditions are fulfilled.