Configuring the safety sensor
Leuze electronic
RSL 410
68
In the RESPONSE TIME dialog box, select the response time of the safety sensor.
In the START-UP BEHAVIOR dialog box, select the start-up behavior and the restart time of the safety
sensor.
Click the [Confirm] button.
Configure all other banks of the protective function following the described procedure.
Create protective and warning fields
A field pair consists of one protective field and one warning field.
In the CONFIGURATION menu, right-click the
Bank 1
option under
Protective function_A
Select
Add field pair
.
The Add field pair dialog box opens.
In the Field pair list, select the number of the field pair and click the [Add] button. When you have added
all field pairs for the bank, click [Close].
The added field pairs are shown in the CONFIGURATION menu as an option under
Bank 1
under
Protec
-
tive function_A
. The
Parameters
option is displayed for each field pair.
Configure protective and warning fields
Defining contours and boundaries for protective field and warning field
1
Toolbar of field editor
2
Display of field coordinates
3
Structure of safety configuration
Figure 9.2: Field editor with toolbar for field definition
In the CONFIGURATION menu, click the field pair the protective and warning fields of which you want
to define.
Click the
button and define the contours and boundaries of the protective field.
If in the
Resolution
and
Max. DTS speed
input fields you select values >0, the application usually
used for the bank is displayed in the
Application
field, e.g.
Point of operation guarding
.
For access guarding, point of operation guarding and danger zone guarding, you must select
Max. DTS speed
= 0!
Configuration of the start-up behavior is only implemented if the corresponding electrical signal
connections exist; see chapter 8 "Electrical connection".
2
3
1