Mounting
Leuze electronic
RSL 410
43
If there is a risk that the safety sensor will be used as a climbing aid, install a suitable physical cover
over the safety sensor.
Align the mounted safety sensor horizontally and vertically using the integrated electronic spirit level.
• For the electronic spirit level to work, the supply voltage of 24 V must be present at the safety sensor.
• The electronic spirit level indicates the vertical (V) and horizontal (H) alignment of the safety sensor.
The spirit level is displayed
• permanently after the end of the booting phase/start phase when starting without configuration
• repeatedly until the end of the booting phase/start phase when starting with configuration
• using the configuration and diagnostics software:
Diagnosis > [Align sensor mechanically] button (
)
• When mounting without a mounting system, the safety sensor can be aligned only slightly along the
horizontal axis.
Attach safety notice stickers to the mounted safety sensor (the stickers are included in the delivery con
-
tents).
Configure the safety sensor with the configuration and diagnostics software; see chapter 9 "Configuring
the safety sensor":
• Observe the information on the response times, the stopping time of the machine and the protective
field dimensioning for your application.
• Determine the size of the protective field on the basis of the mounting location, the calculated safety
distances and additional distances.
• Configure the protective field so that the safety-related switching outputs are switched off from every
accessible point with sufficient minimum distance D.
• Determine the start-up/restart operating mode required for the application.
• If you are using start and/or restart interlock, determine the position for the reset button.
• Many safety-relevant parameters are preset for each application in the configuration and diagnostics
software. Use these preset values where possible.
Create a record document for the device configuration and protective field dimensioning.
• The document must be signed by the person responsible for the configuration.
• Include this document with the machine documentation.
Mark the protective field boundaries on the floor.
You can easily test the safety sensor along this marking.
After mounting, you can electrically connect (see chapter 8 "Electrical connection"), start up, align (see
chapter 10 "Starting up the device"), and check (see chapter 11 "Testing") the safety sensor.