8
3
COMMISSIONING MANUAL
POWERDRIVE MD
Variable speed drive
MENUS AND DIAGRAMS IN ADVANCED SET UP MODE
LEROY-SOMER
3871 en - 2011.05 / h
: Di
g
ital I/O read word
Adjustment range : 0 to 511
This parameter is used to determine the state of the I/O with
a single read operation.
Each bit of this word represents the state of parameters
08.01
to
08.09.
E.g.
DIO1 = 1 = 2
0
= 1
DIO3 = 1 = 2
2
= 4
==> 8.20 = 5
: Di
g
ital in/out 1 destination
Adjustment range :
00.00
to
21.51
Factory setting
:
10.03
: Zero frequency
This parameter is used to select the input destination or
output source of DIO1.
Any unprotected "bit" type parameter can be assigned.
If an unsuitable parameter is addressed to the input or output,
no assignment is taken into account.
: DIO2 input destination or output source
Adjustment range :
00.00
to
21.51
Factory setting
:
01.45
: Reference selector
This parameter is used to select the input destination or
output source of DIO2.
Any non-protected "bit" type parameter can be assigned.
If an unsuitable parameter is addressed to the input or output,
no assignment is taken into account.
: DIO3 input destination or output source
Adjustment range :
00.00
to
21.51
Factory setting
:
01.41
: Reference selector
This parameter is used to select the input destination or
output source of DIO3.
Any non-protected "bit" type parameter can be assigned.
If an unsuitable parameter is addressed to the input or output,
no assignment is taken into account.
: Di
g
ital input 4 destination
Adjustment range :
00.00
to
21.51
Factory setting
:
06.30
: FWD/Stop
This parameter is used to select the destination of input DI4.
Any unprotected "bit" type parameter can be assigned to the
input.
If an unsuitable parameter is addressed, no assignment is
taken into account.
: Di
g
ital input 5 destination
Adjustment range :
00.00
to
21.51
Factory setting
:
06.32
: Rev/Stop
This parameter is used to select the destination of input DI5.
Any non-protected "bit" type parameter can be assigned to
the input.
If an unsuitable parameter is addressed, no assignment is
taken into account.
: Not used
: Relay 1 output source
Adjustment range :
00.00
to
21.51
Factory setting
:
10.01
: Drive healthy
This parameter is used to select the source for the output
relay.
Any non-protected "bit" type parameter can be assigned.
If an unsuitable parameter is addressed, no assignment is
taken into account.
CAUTION:
When the secure disable function is enabled,
08.10
=
Secur. disab. (1), the value of
08.27
is fixed at
10.01
,
and cannot be modified.
: Relay 2 output source
Adjustment range :
00.00
to
21.51
Factory setting
:
10.52
: V
max
alarm
This parameter is used to select the source for the output
relay.
Any non-protected "bit" type parameter can be assigned.
If an unsuitable parameter is addressed, no assignment is
taken into account.
: Di
g
ital input polarity
Adjustment range : NEGATIVE (0) or POSITIVE (1)
Factory setting
: POSITIVE (1)
This parameter is used to change the polarity of digital inputs.
It has no effect when DIO1, DIO2 or DIO3 are programmed
as outputs.
NEGATIVE (0):
Negative logic.
POSITIVE (1): Positive lo
g
ic.
: Not used
: Di
g
ital in/out 1 select
Adjustment range : Input (0) or Output (1)
Factory setting
: Output (1)
Used to configure terminal DIO1 as an input or output.
Input (0): Terminal confi
g
ured as an input.
Output (1):
Terminal configured as an output.
: Di
g
ital in/out 2 select
Adjustment range : Input (0) or Output (1)
Factory setting
: Input (0)
Used to configure terminal DIO2 as an input or output.
Input (0): Terminal confi
g
ured as an input.
Output (1):
Terminal configured as an output.
: Di
g
ital in/out 3 select
Adjustment range : Input (0) or Output (1)
Factory setting
: Input (0)
Used to configure terminal DIO3 as an input or output.
Input (0): Terminal confi
g
ured as an input.
Output (1):
Terminal configured as an output.
to
: Not used
Bit
8
7
6
5
4
3
2
1
0
State
08.0908.0808.07
-
08.0508.0408.0308.0208.01
08.20
08.21
08.22
08.23
08.24
08.25
08.26
08.27
08.28
08.29
08.30
08.31
08.32
08.33
08.34
08.49