114
COMMISSIONING MANUAL
POWERDRIVE MD
Variable speed drive
MENUS AND DIAGRAMS IN ADVANCED SET UP MODE
LEROY-SOMER
3871 en - 2011.05 / h
: Comparator 3 hysteresis
Adjustment range : 0 to 25.0%
Factory setting
: 0
This parameter defines the window within which the
comparator output will not change state.
The output will change to Enabled (1) when the variable
reaches the value of the thr (hysteresis/2).
The output will change to Disabled (0) when the variable goes
below the value of the threshold - (hysteresis/2).
The hysteresis is expressed as a percentage of the maximum
value of the compared variable.
: Comparator 3 output invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
This parameter is used to invert the comparator output.
Disabled (0): Output not inverted.
Enabled (1):
Output inverted.
: Comparator 3 output destination
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter defines the internal parameter which will be
assigned by the comparator output.
Only bit type parameters can be programmed.
If an unsuitable parameter is programmed, the output is not
sent anywhere.
to
: Not used
: Comparator 4 output
Adjustment range : Disabled (0) or Enabled (1)
Disabled (0):
The input variable is less than or equal to the
comparator threshold.
Enabled (1):
The input variable is greater than the
comparator threshold.
: Not used
: Comparator 4 source
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter defines the variable that is to be compared to
the configured threshold.
The absolute value of the variable is used. Only non-bit
parameters can be programmed as the source.
If an unsuitable parameter is programmed, the input value is
taken as equal to 0.
: Comparator 4 threshold
Adjustment range : 0 to 100.0%
Factory setting
: 0
This parameter is used to set the comparator trip threshold.
The threshold is expressed as a percentage of the maximum
value of the compared variable.
: Comparator 4 hysteresis
Adjustment range : 0 to 25.0%
Factory setting
: 0
This parameter defines the window within which the
comparator output will not change state.
The output will change to Enabled (1) when the variable
reaches the value of the thr (hysteresis/2).
The output will change to Disabled (0) when the variable goes
below the value of the threshold - (hysteresis/2).
The hysteresis is expressed as a percentage of the maximum
value of the compared variable.
: Comparator 4 output invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
This parameter is used to invert the comparator output.
Disabled (0): Output not inverted.
Enabled (1):
Output inverted.
: Comparator 4 output destination
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter defines the internal parameter which will be
assigned by the comparator output.
Only bit type parameters can be programmed.
If an unsuitable parameter is programmed, the output is not
sent anywhere.
12.65
12.66
12.67
12.68
12.70
12.71
12.72
12.73
12.74
12.75
12.76
12.77