41
COMMISSIONING MANUAL
POWERDRIVE MD
Variable speed drive
MENUS AND DIAGRAMS IN ADVANCED SET UP MODE
LEROY-SOMER
3871 en - 2011.05 / h
: Preset selector
Adjustment range : Term. inputs (0), Preset 1 (1) to Preset 8
(8),
Timer (9)
Factory setting
: Term. inputs (0)
This parameter is used to select the preset references. It
works as follows:
Term. inputs (0):
Used to select the reference by
combinin
g
the di
g
ital inputs assi
g
ned to parameters
01.45
to
01.47.
Preset 1 (1):
Preset reference 1
Preset 2 (2):
Preset reference 2
Preset 3 (3):
Preset reference 3
Preset 4 (4):
Preset reference 4
Preset 5 (5):
Preset reference 5
Preset 6 (6):
Preset reference 6
Preset 7 (7):
Preset reference 7
Preset
8
(
8
):
Preset reference 8
Timer (9):
The reference is selected automatically by a scan
timer.
: Preset reference timer
Adjustment range : 0 to 9999 s
Factory setting
: 0
When
01.15
= Timer (9) and
01.70
= "Same" (0), is used to
set the time between each reference where the scan time is
identical between each preset reference.
: Keypad reference
Adjustment range : ±
01.06
Indicates the reference value coming from the configuration
interface (see section 2.2.3.4).
to
: Not used
to
: Preset references 1 to
8
Adjustment range : ±
01.06
Factory setting
: 0
In order,
01.21
to
01.28
are used to define preset
references Preset 1 to Preset 8.
and
: Skip references 1 and 2
Adjustment range : 0 to 32000 rpm
Factory setting
: 0
Two skips are available to avoid a machine running at critical
speeds. When one of these parameters is at 0, the
corresponding skip reference is deactivated.
and
: Skip reference bands 1 and 2
Adjustment range : 0 to 300 rpm
Factory setting
: 15 rpm
Define the skip band around the avoided speed. The total skip
will therefore equal the threshold set ± skip reference band.
When the reference is within the window determined in this
way, the drive will not allow operation in this zone.
and
: Not used
: Reference in skip zone
Adjustment range : Out (0) or In (1)
This parameter is In (1) when the selected reference is within
one of the skip zones.
In this case, the motor speed does not correspond to the
requested reference.
and
: Analo
g
references 1 and 2
Adjustment range :
01.07
to
01.06
(
01.10
= 0)
±
01.06
(
01.10
= 1)
The analog inputs assigned to these parameters are
automatically scaled so that 100.0% of the input corresponds
to the maximum reference (
01.06
). Similarly the 0% input
level will correspond to the minimum reference
01.07
or
0 according to
01.10
.
Unipolar mode (
01.10
= 0)
Bipolar mode (
01.10
= 1)
: Percenta
g
e trim
Adjustment range : ± 100.0%
An offset proportional to the selected reference can be added
to this reference.
The multiplication coefficient is determined by the analog
input assigned to
01.38
.
Final ref =
and
: Not used
and
: Reference selection usin
g
di
g
ital inputs
Adjustment range: Off (0) or On (1)
Used to assign the digital inputs to selection of the speed
reference.
01.41
: bit 0
01.42
: bit 1
and
: Not used
01.15
01.16
01.17
01.18
01.20
01.21
01.28
01.29
01.31
01.30
01.32
01.33
01.34
01.42 01.41
Selected reference
01.49
0
0
Analog input 1
1
0
1
Analog input 2
2
1
0
Preset references
3
1
1
Reference via the keypad
4
01.35
01.36
01.37
Reference
01.06
01.07
0
100.0
%
Reference
01.06
01.06
- 100.0
+ 100.0
%
01.38
ref sélectionnée x (
01.38
+ 100)
100
01.39
01.40
01.41
01.42
01.43
01.44