71
COMMISSIONING MANUAL
POWERDRIVE MD
Variable speed drive
MENUS AND DIAGRAMS IN ADVANCED SET UP MODE
LEROY-SOMER
3871 en - 2011.05 / h
: Run time: hours, minutes
Adjustment range : 0 to 23, 59 (hrs, min)
This parameter records the number of hours and minutes of
operation since the drive was first commissioned.
After 23, 59,
06.23
returns to 0 and
06.22
is incremented by
one day.
: Ener
g
y meter: MWh
Adjustment range : 0 to 999.9 MWh
This parameter records the drive energy consumption in
MWh.
This meter can be reset to 0 by changing parameter
06.17
to
Enabled (1).
: Ener
g
y meter: kWh
Adjustment range : 0 to 99.99 kWh
This parameter records the drive energy consumption in kWh.
This meter can be reset to 0 by changing parameter
06.17
to
Enabled (1).
to
: Not used
to
and :
Se
q
uencin
g
bits for
lo
g
ic commands
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
The drive's logic command manager (
06.04
) uses these bits
as inputs rather than referring directly to the terminals. This
enables the user to define the use for each drive terminal
according to the needs of each application. Although these
are read/write type parameters, they are volatile and are not
stored when the drive is powered down. Each time the drive
is powered up they will be reset to Disabled (0).
06.30
: Run FWD sequencing bit
06.31
: Jog sequencing bit
06.32
: Run Reverse sequencing bit
06.33
: FWD/Reverse sequencing bit
06.34
: Run/Stop sequencing bit
06.39
: Stop sequencing bit
to
: Not used
: Control word
Adjustment range : 0 to 32767
Factory setting
: 0
The control word is used to control the drive via a serial link.
Each function has a corresponding binary code:
06.42
should correspond to the binary sum of the commands
to be given to the drive.
So that the control word is taken into account, parameter
06.43
should be at 1.
Note:
For enabling the drive by enabling
06.15
(Bit 0), the
enabling terminal of the terminal block must previously have
been activated (see explanation of
06.15
).
06.23
06.24
06.25
06.26
06.29
06.30
06.34
06.39
06.35
06.41
Control
word
bits
06.42
Decimal
conversion
Functions
E
q
uivalent
parameter
0
1
Drive enable
06.15
1
2
Run forward
06.30
2
4
Jog indicator
06.31
3
8
Run reverse
06.32
4
16
Forward/Reverse
06.33
5
32
Run
06.34
6
64
Reserved
7
128
Reserved
8
256
Analog ref./
Preset ref.
01.42
9
512
Reserved
10
1024
Reserved
11
2048
Reserved
12
4096
Reserved
13
8192
Drive reset
10.33
14
16384
Reserved
06.42