Control connections
3
8
MA DrivePLC DE/EN/FR 1.0
Terminal strips on the top of the instrument
l
The Drive PLC can only be connected to a supply voltage of max. + 30 V DC !
l
Higher voltages, or AC, will destroy the instrument !
plc002
X3
I8
I4
I7
I3
I6
I2
I5
I1
3K
3K
3K
3K
3K
3K
3K
3K
X2 O1 O2 O3 O4
+
~
~
-
X1 +O24 +24
24
Z Z Z Z
Abb. 1-18
Connection required
Possible connection
Encoder
ó
Load
ì
Emergency off
ö
External DC supply voltage
ú
Supply for control electronics
Terminal Use
level
Data
Voltage
supply
X1/
⊥
24
0 V of supply voltage,
ground for digital inputs
and outputs
-
-
X1/+ 24
Supply voltage
+ 18 VDC ... 30 VDC
-
X1/+ O24 Supply voltage for digital
outputs
+ 18 VDC ... 30 VDC
-
Digital
inp ts
X3/I1
Freely assignable input 1
HIGH active
Input current: 8 mA at 24 V
Reading and processing the
inputs
HIGH active
LOW: 0 V ... + 4 V
HIGH
13 V
30 V
Reading and processing the
inputs: shortest reading cycle: 1
ms (depending on the site where
X3/I8
Freely assignable input 8
HIGH: + 13 V ... + 30 V
p
g y
ms (depending on the site where
the process map is generated)
Digital
outputs
X2/O1
Freely assignable output 1
HIGH active
Load capacity: max. 1 A per
output
outputs
HIGH active
LOW: 0 V ... + 4 V
HIGH: + 13 V
+ 30 V
output
Updating the outputs: shortest
update cycle is 1 ms (depending
X2/O4
HIGH: + 13 V ... + 30 V
update cycle is 1 ms (depending
on the site where the process
map is generated)