Technical data
2
MA DrivePLC DE/EN/FR 1.0
3
General data / Application conditions
Approvals
UL 508:
Industrial Control Equipment (in preparation)
DC voltage supply
Voltage
+ 18 VDC ... 30 VDC
DC voltage supply
Current
200 mA at + 24 V (without load at the outputs)
Ambient temperature
transport
-25 °C ... + 70 °C
Ambient temperature
storage
-25 °C ... + 60 °C
Operation
0 °C ... + 55 °C
Permissible mounting positions
vertical
Installation space
≥
100 mm above and below
Type of protection
IP 20
PLC functionality
Field
Number Description
Data
Inputs
digital
8 Free inputs
+ 24 VDC / 8 mA per
input
Reading and writing of the
inputs:
Shortest reading cycle: 1 ms
(depending on the site where
the process map is
generated)
analog
3 Free inputs
(10 bit + sign)
± 10 V
Outputs
digital
4 Free outputs
+ 24 VDC / max. 1 A
per output
Updating the outputs:
shortest update cycle is 1 ms
(depending on the site where
the process map is
generated)
analog
1 Voltage output (10 bits +
sign)
± 10 V / max. 2 mA
1 Current output
(10 bits + sign)
± 20 mA
Show/Hide Bookmarks