Monitoring functions
Configuring monitoring functions
Monitoring of the absolute value encoder initialisation (Sd7)
220
EDBCSXS064 EN 4.0
9.3.16
Monitoring of the absolute value encoder initialisation (Sd7)
Fault message
Monitoring function
System variable
Possible response
TRIP
Messag
e
Warnin
g
Off
087
Sd7
Absolute value encoder
initialisation error
MCTRL_bEncoderFault_b
·
·
Default setting
ü
Setting possible
When the ECSxS... axis module is switched on, this monitoring function repeatedly
downloads the absolute value of the hiperface absolute value encoder to identify whether
the same value is transferred to the drive.
The absolute value encoders (single−turn, multi−turn) are supported by a hiperface
interface with various numbers of increments, e.g.: SRM50 with 1024 Sin/Cos periods/rev.
or SKM38 with 128 periods/rev.(see also C0419).
If a deviation > 5° on the motor shaft is detected, the monitoring (TRIP) is actuated.
The fault message "Sd7" can only be reset by mains switching!