Monitoring
functions
Overview of monitoring functions
9
195
EDBCSXS064
EN 4.0
Possible fault responses
l
Lenze setting
ü
Can be set
Monitoring
Off
Fail−QSP
Warning
Message
TRIP
Code
Source
Description
Fault message
x126
CE15
Communication error of the gateway function via CAN bus at interface X14
(CAN−AUX)
l
C0371 = 1: Gateway channel X14 (CAN−AUX)
l
C2470: Selection of the CANaux object for L_ParRead and L_ParWrite
CANaux
C2485
ü
ü
l
x260
Err Node
Guard
"Life Guarding Event":
The controller configured as CAN slave does not receive a "Node Guarding"
telegram with the "Node Life Time" from the CAN master.
Node
Guarding
C0384
l
ü
ü
ü
2)
ü
Temperatures / sensors
0050
OH
Device heatsink temperature > 90° C
MCTRL
l
0051
OH1
Temperature inside the device > 90° C
MCTRL
l
x053
OH3
Motor temperature > 150° C
MCTRL
C0583
l
ü
ü
x054
OH4
Heatsink temperature > C0122
MCTRL
C0582
ü
l
ü
x055
OH5
Temperature inside the device > C0124
MCTRL
C0605
ü
l
ü
x057
OH7
Motor temperature > C0121
MCTRL
C0584
ü
l
ü
x058
OH8
Motor temperature via inputs T1 and T2 is too high.
MCTRL
C0585
ü
l
ü
x086
Sd6
Thermal sensor error on the motor (X7 or X8)
MCTRL
C0594
ü
ü
l
x095
FAN1
Devicefan monitoring (only for built−in units)
ü
l
x110
H10
Device thermal sensor error on heatsink
FWM
C0588
l
ü
x111
H11
Device thermal sensor error in the interior of the device
FWM
C0588
l
ü
Motor / feedback system
0011
OC1
Short circuit of motor cable
MCTRL
l
0012
OC2
Motor cable earth fault
MCTRL
l
0015
OC5
Device utilisation I x t (fix 100%)
MCTRL
l
0016
OC6
Motor utilisation I
2
x t (threshold C0120)
MCTRL
l
x017
OC7
Device utilisation I x t (clip C0123)
MCTRL
C0604
ü
l
ü
x018
OC8
Motor utilisation I
2
x t (threshold C0127)
MCTRL
C0606
ü
l
ü
x032
LP1
Motor phase failure
Note:
Can only be used for asynchronous motors. Activation of the motor
phase failure detection minimises the computing time available to the
user!
MCTRL
C0597
ü
ü
l
x081
Rel1
Open circuit monitoring of the brake relay output (X25)
FWM
C0602
ü
ü
ü
l
x082
Sd2
Resolver error at X7
Note:
If monitoring is switched off or in the case of "Warning", the machine
can reach very high speeds in the case of fault, which may result in the
damage of the motor and the machine that is driven!
MCTRL
C0586
l
ü
ü
x: 0 = TRIP, 1 = message, 2 = warning, 3 = FAIL−QSP
1)
Adjustable in the DDS under
Project
Exceptional handling
2)
For ECSxA... only