background image

Page 4

506083−01 03/08

 SERVICE PORT

SERVICE PORT

CORE

TO OUTDOOR UNIT

STEM CAP

(VALVE STEM SHOWN OPEN)

INSERT HEX WRENCH HERE

SERVICE PORT CAP

TO INDOOR

UNIT

VALVE IS BACK−SEATED

(OPENED)

OPEN TO BOTH

INDOOR AND

OUTDOOR UNITS

Figure 4. 

Angle−Type Service Valve 

(Back−Seated Opened)

Operating Ball−Type Service Valve

To Access Ball−Type Service Port:

A service port cap protects the service port core from
contamination and serves as the primary leak seal.

BALL (SHOWN
CLOSED)

SERVICE PORT

CORE

TO INDOOR UNIT

TO OUTDOOR UNIT

Use appropriately sized
wrench.

To 

open

 rotate stem

counterclockwise 90°.
To 

close 

rotate stem clockwise

90°.

SERVICE PORT

SERVICE PORT CAP

STEM CAP

VALVE
STEM

Open to line set when valve is closed, to
both line set and unit when valve is open.

Figure 5. Ball−Type Service Valve

1. Remove service port cap with an appropriately sized

wrench.

2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and

tighten as follows:

With Torque Wrench

: Finger tighten and then

tighten per table 1.

Without Torque Wrench

: Finger tighten and use an

appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 2.

To Open and Close Ball−Type Service Valve:

A valve stem cap protects the valve stem from
contamination and assures a leak−free seal.

1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrench to open. To open

valve, rotate stem counterclockwise 90°. To close
rotate stem clockwise 90°.

3. Replace the stem cap and tighten as follows:

With Torque Wrench

: Finger tighten and then

tighten per table 1.

Without Torque Wrench

: Finger tighten and use an

appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 2.

NOTE − A label with specific torque requirements may be
affixed to the stem cap. If the label is present, use the
specified torque.

Recovering Refrigerant from Existing
HCFC−22 System

Remove existing HCFC−22 refrigerant using the following
procedures:

METHOD 1:

If the existing outdoor unit is not equipped with shut−off
valves, or if the unit is not operational and you plan to use
the existing HCFC−22 refrigerant to flush the system, then:

NOTE − Use recovery machine instructions for specific
setup requirements.

1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean

recovery cylinder and a recovery machine. Use the
instructions provided with the recovery machine on
how to setup the connections.

3. Remove all HCFC−22 refrigerant from the existing

system. Check gauges after shutdown to confirm that
the entire system is completely void of refrigerant.

MANIFOLD GAUGES

RECOVERY MACHINE

CLEAN RECOVERY
CYLINDER

OUTDOOR UNIT

Figure 6. Typical Refrigerant Recovery (Method 1)

NOTE − Use recovery machine instructions for specific
setup requirements.

METHOD 2:

If the existing outdoor unit is equipped with manual shut−off
valves and you plan to use new HCFC−22

 

refrigerant to

flush the system then:

1. Start the existing HCFC−22 system in the cooling

mode and close the liquid line valve.

2. Pump all of the existing HCFC−22 refrigerant back into

the outdoor unit.

NOTE − It may be necessary to bypass the low pressure
switches to ensure complete refrigerant evacuation.

Содержание TSA036H4N41

Страница 1: ...41 TSA048H4N41 and TSA060H4N41 AIR CONDITIONER 506083 01 03 08 Table of Contents Shipping and Packing List 1 TSA H4 Air Conditioners 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant fr...

Страница 2: ...ble 1 shows torque values for fasteners Table 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 in lb 2 NM Machine screws 10 28 in lb 3 NM Compressor...

Страница 3: ...nd use an appropriately sized wrench to turn an additional 1 6 turn clockwise as illustrated in figure 2 To Open and Close Angle Type Service Valve A valve stem cap protects the valve stem from contam...

Страница 4: ...as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench to turn an additional 1 12 turn clockwise as illus...

Страница 5: ...CONSIDERATIONS Consider the following when positioning the unit Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the install...

Страница 6: ...ne that ran from condenser to evaporator coil Refrigerant was metered into the evaporator by utilizing temperature pressure evaporation effects on refrigerant in the small RFC line The length and bore...

Страница 7: ...caps or service valve stub caps until you are ready to make connections WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubi...

Страница 8: ...nnect manifold gauge set from service ports cool down piping with wet rag and remove all wrappings Do not reinstall cores until after evacuation procedure Reinstall service caps if desired to close of...

Страница 9: ...ushing Existing System IMPORTANT The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushin...

Страница 10: ...gerant to flow into the system through the suction line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine 4...

Страница 11: ...aining Teflon washer around the other end of the TXV Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil 5 Attach the liquid line assembly to the TXV Finger...

Страница 12: ...or unit 6 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be detected NOTE Amounts of refrigerant will vary with line lengths 7 Check all joints for leak...

Страница 13: ...to break the vacuum and install a new filter drier in the system 4 Evacuate the system again Then weigh the appropriate amount of HFC 410A refrigerant as listed on unit nameplate into the system 5 Mo...

Страница 14: ...e only with copper conductors NOTE A complete unit wiring diagram is located inside the unit control box cover NOTE See unit wiring diagram for power supply connections If indoor unit is not equipped...

Страница 15: ...ine service port INDOOR COIL AIRFLOW CHECK Check indoor coil airflow using the Delta T DT process as illustration in figure 27 DETERMINING CHARGE METHOD To determine the correct charging method use th...

Страница 16: ...utdoor ambient temperature 64 F and BELOW 1 Check Liquid and suction line pressures 2 Compare unit pressures with Table 27 Normal Operating Pressures 3 Conduct leak check evacuate as previously outlin...

Страница 17: ...erant If refrigerant is added or removed verify charge using the Approach Method 64 F and BELOW 65 F and ABOVE ABOVE or BELOW F C 036 042 048 060 65 18 13 7 2 10 5 6 8 4 4 8 4 4 75 24 9 5 0 7 3 9 8 4...

Страница 18: ...7 190 9 83 246 5 98 308 2 114 385 4 129 469 5 145 572 8 37 111 4 53 150 1 68 194 1 84 250 3 99 312 7 115 390 7 130 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147...

Страница 19: ...ineering Handbook for optional accessories that may apply to this unit The following may or may not apply Timed Off Control Sound Cover Suction Line Drier Stand Off Kit Low Ambient Kit Homeowner Infor...

Страница 20: ...vides temporary heat supplied by the auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperatu...

Отзывы: