background image

Page 6

506083−01 03/08

New or Replacement Line Set

This section provides information on installation or
replacement of existing line set. If line set is not being
installed or replace then proceed to 

Brazing Connections

on page 7.

If refrigerant lines are routed through a wall, seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds.

Also, consider the following when placing and installing a
high−efficiency air conditioner:

REFRIGERANT LINE SET

Field refrigerant line set consists of liquid and suction lines
from the outdoor unit (braze connections) to the indoor unit
coil (flare or braze connections). Use Lennox L15 (braze,
non−flare) series line set, or use field−fabricated refrigerant
lines as listed below.

Table 2. Refrigerant Line Set

Models

Field
Connections

Recommended Line Set

Liquid
Line

Suction
Line

Liquid
Line

Suction
Line

L15
Line Set

−036
−042
−048

3/8 in.
(10 mm)

7/8 in
(22 mm)

3/8 in.
(10
mm)

7/8 in
(22 mm)

L15−65
15 ft. − 50 ft.
(4.6 m − 15 m)

−060

3/8 in.
(10 mm)

1−1/8 in.
(29 mm)

3/8 in.
(10
mm)

1−1/8 in.
(29 mm)

Field
Fabricated

NOTE − When installing refrigerant lines longer than 50
feet, contact Lennox Technical Support Product
Applications for assistance or Lennox piping manual. To
obtain the correct information from Lennox, be sure to
communicate the following points:

Model (TSA*H4) and size of unit (e.g. −060).

Line set diameters for the unit being installed as listed
in table 2 and total length of installation.

Number of elbows and if there is a rise or drop of the
piping.

MATCHING WITH NEW OR EXISTING INDOOR COIL
AND LINE SET

The RFC1−metering line consisted of a small bore copper
line that ran from condenser to evaporator coil. Refrigerant
was metered into the evaporator by utilizing
temperature/pressure evaporation effects on refrigerant in
the small RFC line. The length and bore of the RFC line
corresponded to the size of cooling unit.

If the TSA*H4 is being used with either a new or existing
indoor coil which is equipped with a liquid line which served
as a metering device (RFCI), the liquid line must be
replaced prior to the installation of the TSA*H4 unit.

Typically a liquid line used to meter flow is 1/4" in diameter
and copper.

LIQUID LINE FILTER DRIER INSTALLATION

The filter drier (one is shipped with each TSA*H4 unit)
must be field installed in the liquid line between the outdoor
unit’s liquid line service valve and the indoor coil’s
expansion valve. This filter drier must be installed to
ensure a clean, moisture−free system. Failure to install the
filter drier will void the warranty. A replacement filter drier is
available from Lennox. See 

Brazing Connections

 on page

7 for special procedures on brazing.

OUTDOOR

UNIT

LIQUID LINE

SERVICE VALVE

LIQUID LINE

FILTER DRIER

LINE

LIQUID

LINE

BRAZE CONNECTION

POINTS

Figure 10. Typical Liquid Line Filter Drier

Installation

INSTALLING LINE SET
Line Set Isolation

This reference illustrates

procedures, which ensure proper refrigerant line set
isolation:

Installation of 

line set on horizontal runs

 is

illustrated in figure 11.

Installation of

 line set on vertical runs

 is illustrated in

figure 12.

Installation of a 

transition from vertical to

horizontal 

is illustrated in figure 13.

METAL

SLEEVE

STRAPPING MATERIAL

(AROUND SUCTION

LINE ONLY)

TAPE OR

WIRE TIE

WIRE TIE
(AROUND
SUCTION LINE
ONLY)

FLOOR JOIST OR

ROOF RAFTER

TAPE OR

WIRE TIE

To hang line set from joist or rafter,
use either metal strapping material
or anchored heavy nylon wire ties.

8 FEET

8 FEET

Strap the suction line to the
joist or rafter at 8 feet
intervals then strap the
liquid line to the suction line.

FLOOR JOIST OR

ROOF RAFTER

Figure 11. Refrigerant Line Set: Installing 

Horizontal Runs

Содержание TSA036H4N41

Страница 1: ...41 TSA048H4N41 and TSA060H4N41 AIR CONDITIONER 506083 01 03 08 Table of Contents Shipping and Packing List 1 TSA H4 Air Conditioners 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant fr...

Страница 2: ...ble 1 shows torque values for fasteners Table 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 in lb 2 NM Machine screws 10 28 in lb 3 NM Compressor...

Страница 3: ...nd use an appropriately sized wrench to turn an additional 1 6 turn clockwise as illustrated in figure 2 To Open and Close Angle Type Service Valve A valve stem cap protects the valve stem from contam...

Страница 4: ...as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench to turn an additional 1 12 turn clockwise as illus...

Страница 5: ...CONSIDERATIONS Consider the following when positioning the unit Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the install...

Страница 6: ...ne that ran from condenser to evaporator coil Refrigerant was metered into the evaporator by utilizing temperature pressure evaporation effects on refrigerant in the small RFC line The length and bore...

Страница 7: ...caps or service valve stub caps until you are ready to make connections WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubi...

Страница 8: ...nnect manifold gauge set from service ports cool down piping with wet rag and remove all wrappings Do not reinstall cores until after evacuation procedure Reinstall service caps if desired to close of...

Страница 9: ...ushing Existing System IMPORTANT The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushin...

Страница 10: ...gerant to flow into the system through the suction line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine 4...

Страница 11: ...aining Teflon washer around the other end of the TXV Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil 5 Attach the liquid line assembly to the TXV Finger...

Страница 12: ...or unit 6 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be detected NOTE Amounts of refrigerant will vary with line lengths 7 Check all joints for leak...

Страница 13: ...to break the vacuum and install a new filter drier in the system 4 Evacuate the system again Then weigh the appropriate amount of HFC 410A refrigerant as listed on unit nameplate into the system 5 Mo...

Страница 14: ...e only with copper conductors NOTE A complete unit wiring diagram is located inside the unit control box cover NOTE See unit wiring diagram for power supply connections If indoor unit is not equipped...

Страница 15: ...ine service port INDOOR COIL AIRFLOW CHECK Check indoor coil airflow using the Delta T DT process as illustration in figure 27 DETERMINING CHARGE METHOD To determine the correct charging method use th...

Страница 16: ...utdoor ambient temperature 64 F and BELOW 1 Check Liquid and suction line pressures 2 Compare unit pressures with Table 27 Normal Operating Pressures 3 Conduct leak check evacuate as previously outlin...

Страница 17: ...erant If refrigerant is added or removed verify charge using the Approach Method 64 F and BELOW 65 F and ABOVE ABOVE or BELOW F C 036 042 048 060 65 18 13 7 2 10 5 6 8 4 4 8 4 4 75 24 9 5 0 7 3 9 8 4...

Страница 18: ...7 190 9 83 246 5 98 308 2 114 385 4 129 469 5 145 572 8 37 111 4 53 150 1 68 194 1 84 250 3 99 312 7 115 390 7 130 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147...

Страница 19: ...ineering Handbook for optional accessories that may apply to this unit The following may or may not apply Timed Off Control Sound Cover Suction Line Drier Stand Off Kit Low Ambient Kit Homeowner Infor...

Страница 20: ...vides temporary heat supplied by the auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperatu...

Отзывы: