background image

Page 14

506083−01 03/08

5. Install low−voltage wiring from outdoor to indoor unit

and from thermostat to indoor unit.

R

W1

Y

G

C

R

W

Y

G

C

THERMOSTAT

INDOOR UNIT

POWER

HEAT

COOLING

INDOOR BLOWER

COMMON

OUTDOOR UNIT

Y1

C

Figure 25. Low Voltage Wiring Diagram

(Typical Field Wiring)

Table 3. Wire Run Lengths

Wire Run Length

AWG #

Insulation Type

Less than 100 feet
(30m)

18

Color−coded with a
minimum temperature
rating of 35

º

C.

More than 100 feet
(30m)

16

6. Do not bundle any excess 24V control wire inside

control box. Run control wire through installed wire tie
and tighten wire tie to provided low voltage strain relief
and to maintain separation of field installed low and
high voltage circuits as illustrated in figure 25.

NOTE − 

24VAC, Class II circuit connections are made in

the low voltage junction box

NOTE − To facilitate conduit, a hole is in the bottom of the
control box. Connect conduit to the control box using a
proper conduit fitting.

NOTE − Units are approved for use only with copper
conductors.

NOTE − A complete unit wiring diagram is located inside
the unit control box cover.

NOTE − See unit wiring diagram for power supply
connections. If indoor unit is not equipped with blower
relay. It must be field−provided and installed (P−8−3251 or
equivalent)

THREE-PHASE SCROLL VOLTAGE PHASING

Three-phase scroll compressors must be phased
sequentially to ensure correct compressor rotation and
operation. Incorrect line voltage phasing may cause
compressor damage and abnormal unit operation. Power
wires are color-coded as follows: Line 1 − red, line 2 − yellow,
line 3 − blue.

1. 

Cooling demand imitates a 24VAC signal from Y1 in the thermostat.

2. 

24VAC from indoor unit Y1 energizes contacts K1−1, K1−2 and K1−3.

3. 

K1−1, K1−2 and K1−3 N.O. close, energizing compressor B1 and
outdoor fan motor B4.

END  OF  COOLING DEMAND:

1. 

Cooling demand is satisfied. Terminal Y1 is de−energized.

2. 

Compressor contacts K1−1, K1−2 and K1−3 are de−energized.

3. K1−1, 

K1−2 and K1−3 open and compressor B1 and outdoor fan motor

B4 are de−energized and stop immediately.

COOLING:

Note: The thermostat used may be electro−me-
chanical or electronic.

Figure 26. Typical Unit Wiring Diagram

Содержание TSA036H4N41

Страница 1: ...41 TSA048H4N41 and TSA060H4N41 AIR CONDITIONER 506083 01 03 08 Table of Contents Shipping and Packing List 1 TSA H4 Air Conditioners 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant fr...

Страница 2: ...ble 1 shows torque values for fasteners Table 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 in lb 2 NM Machine screws 10 28 in lb 3 NM Compressor...

Страница 3: ...nd use an appropriately sized wrench to turn an additional 1 6 turn clockwise as illustrated in figure 2 To Open and Close Angle Type Service Valve A valve stem cap protects the valve stem from contam...

Страница 4: ...as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench to turn an additional 1 12 turn clockwise as illus...

Страница 5: ...CONSIDERATIONS Consider the following when positioning the unit Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the install...

Страница 6: ...ne that ran from condenser to evaporator coil Refrigerant was metered into the evaporator by utilizing temperature pressure evaporation effects on refrigerant in the small RFC line The length and bore...

Страница 7: ...caps or service valve stub caps until you are ready to make connections WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubi...

Страница 8: ...nnect manifold gauge set from service ports cool down piping with wet rag and remove all wrappings Do not reinstall cores until after evacuation procedure Reinstall service caps if desired to close of...

Страница 9: ...ushing Existing System IMPORTANT The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushin...

Страница 10: ...gerant to flow into the system through the suction line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine 4...

Страница 11: ...aining Teflon washer around the other end of the TXV Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil 5 Attach the liquid line assembly to the TXV Finger...

Страница 12: ...or unit 6 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be detected NOTE Amounts of refrigerant will vary with line lengths 7 Check all joints for leak...

Страница 13: ...to break the vacuum and install a new filter drier in the system 4 Evacuate the system again Then weigh the appropriate amount of HFC 410A refrigerant as listed on unit nameplate into the system 5 Mo...

Страница 14: ...e only with copper conductors NOTE A complete unit wiring diagram is located inside the unit control box cover NOTE See unit wiring diagram for power supply connections If indoor unit is not equipped...

Страница 15: ...ine service port INDOOR COIL AIRFLOW CHECK Check indoor coil airflow using the Delta T DT process as illustration in figure 27 DETERMINING CHARGE METHOD To determine the correct charging method use th...

Страница 16: ...utdoor ambient temperature 64 F and BELOW 1 Check Liquid and suction line pressures 2 Compare unit pressures with Table 27 Normal Operating Pressures 3 Conduct leak check evacuate as previously outlin...

Страница 17: ...erant If refrigerant is added or removed verify charge using the Approach Method 64 F and BELOW 65 F and ABOVE ABOVE or BELOW F C 036 042 048 060 65 18 13 7 2 10 5 6 8 4 4 8 4 4 75 24 9 5 0 7 3 9 8 4...

Страница 18: ...7 190 9 83 246 5 98 308 2 114 385 4 129 469 5 145 572 8 37 111 4 53 150 1 68 194 1 84 250 3 99 312 7 115 390 7 130 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147...

Страница 19: ...ineering Handbook for optional accessories that may apply to this unit The following may or may not apply Timed Off Control Sound Cover Suction Line Drier Stand Off Kit Low Ambient Kit Homeowner Infor...

Страница 20: ...vides temporary heat supplied by the auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperatu...

Отзывы: