background image

Page 10

506083−01 03/08

Two gauge sets (one for HCFC−22; one for
HFC−410A).

LOW

PRESSURE

HIGH

PRESSURE

EXISTING

INDOOR

UNIT

GAUGE

MANIFOLD

INVERTED HCFC−22 CYLINDER
CONTAINS CLEAN HCFC−22 TO
BE USED FOR FLUSHING.

LIQUID LINE SERVICE VALVE

INLET

DISCHARGE

TANK
RETURN

CLOSED

OPENED

RECOVERY

CYLINDER

NOTE − The inverted HCFC−22 cylinder must contain at least the same
amount of refrigerant as was recovered from the existing system.

RECOVERY MACHINE

NEW

OUTDOOR

UNIT

SUCTION LINE

SERVICE VALVE

SUCTION

LIQUID

Figure 18. Typical Flushing Connection

FLUSHING PROCEDURE

1. Connect the following:

HCFC−22 cylinder with clean refrigerant to the
suction service valve,

HCFC−22 gauge set to the liquid line valve,

Recovery machine with an empty recovery tank to
the gauge set.

2. Set the recovery machine for liquid recovery and start

the recovery machine. Open the gauge set valves to
allow the recovery machine to pull a vacuum on the
existing system line set and indoor unit coil.

3. Invert the cylinder of clean HCFC−22 and open its

valve to allow liquid refrigerant to flow into the system
through the suction line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the
indoor unit coil before it enters the recovery machine.

4. After all of the liquid refrigerant has been recovered,

switch the recovery machine to suction recovery so
that all of the HCFC−22 is recovered. Allow the
recovery machine to pull a vacuum on the system.

5. Close the valve on the inverted HCFC−22 drum and

the gauge set valves. Pump the remaining refrigerant
out of the recovery machine and turn the machine off.

6. Use dry nitrogen to break the vacuum on the

refrigerant lines and indoor unit coil before removing
the recovery machine, gauges and HCFC−22
refrigerant drum.

Installing New Indoor Unit Metering 
Device 

TSA*H4 units are used in thermal expansion valve (TXV)
systems only.

1

2

3

4

5

6

7

8

9

10

11

12

1/8 TURN

1

2

3

4

5

6

7

8

9

10

11

12

1/2 TURN

Figure 19.  Tightening Distance

TSA*H4

 

ENGINEERING HANDBOOK

See the TSA*H4 

Engineering Handbook

 for approved

indoor/outdoor match−ups, applicable TXV kit, and
application information. 

Figure 20 illustrates the typical TXV kit parts and
quantities.

TXV (1)

COPPER

MOUNTING

STRAP (1)

HEX HEAD BOLTS

AND NUTS (2)

TEFLON
RINGS (2)

Figure 20. TXV Kit Components

Содержание TSA036H4N41

Страница 1: ...41 TSA048H4N41 and TSA060H4N41 AIR CONDITIONER 506083 01 03 08 Table of Contents Shipping and Packing List 1 TSA H4 Air Conditioners 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant fr...

Страница 2: ...ble 1 shows torque values for fasteners Table 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 in lb 2 NM Machine screws 10 28 in lb 3 NM Compressor...

Страница 3: ...nd use an appropriately sized wrench to turn an additional 1 6 turn clockwise as illustrated in figure 2 To Open and Close Angle Type Service Valve A valve stem cap protects the valve stem from contam...

Страница 4: ...as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench to turn an additional 1 12 turn clockwise as illus...

Страница 5: ...CONSIDERATIONS Consider the following when positioning the unit Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the install...

Страница 6: ...ne that ran from condenser to evaporator coil Refrigerant was metered into the evaporator by utilizing temperature pressure evaporation effects on refrigerant in the small RFC line The length and bore...

Страница 7: ...caps or service valve stub caps until you are ready to make connections WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubi...

Страница 8: ...nnect manifold gauge set from service ports cool down piping with wet rag and remove all wrappings Do not reinstall cores until after evacuation procedure Reinstall service caps if desired to close of...

Страница 9: ...ushing Existing System IMPORTANT The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushin...

Страница 10: ...gerant to flow into the system through the suction line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine 4...

Страница 11: ...aining Teflon washer around the other end of the TXV Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil 5 Attach the liquid line assembly to the TXV Finger...

Страница 12: ...or unit 6 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be detected NOTE Amounts of refrigerant will vary with line lengths 7 Check all joints for leak...

Страница 13: ...to break the vacuum and install a new filter drier in the system 4 Evacuate the system again Then weigh the appropriate amount of HFC 410A refrigerant as listed on unit nameplate into the system 5 Mo...

Страница 14: ...e only with copper conductors NOTE A complete unit wiring diagram is located inside the unit control box cover NOTE See unit wiring diagram for power supply connections If indoor unit is not equipped...

Страница 15: ...ine service port INDOOR COIL AIRFLOW CHECK Check indoor coil airflow using the Delta T DT process as illustration in figure 27 DETERMINING CHARGE METHOD To determine the correct charging method use th...

Страница 16: ...utdoor ambient temperature 64 F and BELOW 1 Check Liquid and suction line pressures 2 Compare unit pressures with Table 27 Normal Operating Pressures 3 Conduct leak check evacuate as previously outlin...

Страница 17: ...erant If refrigerant is added or removed verify charge using the Approach Method 64 F and BELOW 65 F and ABOVE ABOVE or BELOW F C 036 042 048 060 65 18 13 7 2 10 5 6 8 4 4 8 4 4 75 24 9 5 0 7 3 9 8 4...

Страница 18: ...7 190 9 83 246 5 98 308 2 114 385 4 129 469 5 145 572 8 37 111 4 53 150 1 68 194 1 84 250 3 99 312 7 115 390 7 130 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147...

Страница 19: ...ineering Handbook for optional accessories that may apply to this unit The following may or may not apply Timed Off Control Sound Cover Suction Line Drier Stand Off Kit Low Ambient Kit Homeowner Infor...

Страница 20: ...vides temporary heat supplied by the auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperatu...

Отзывы: