background image

Page 11

TSA*H4 SERIES

TYPICAL TXV INSTALLATION PROCEDURE

The TXV unit can be installed internal or external to the
indoor coil. In applications where an uncased coil is being
installed in a field−provided plenum, install the TXV and
provide an access for field servicing of the TXV. Refer to
Figure 21 for reference during installation of TXV unit.

TWO PIECE

PATCH PLATE

(UNCASED COIL

ONLY)

SUCTION
LINE

LIQUID LINE

ORIFICE

HOUSING

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER LINE

FITTING (SEE FIGURE 23
FOR FURTHER DETAILS)

SENSING

LINE

EQUALIZER
LINE

TXV

TEFLON
RING

(Uncased Coil Shown)

SENSING BULB INSULATION IS REQUIRED
IF MOUNTED EXTERNAL TO THE COIL
CASING. SEE FIGURE 22 FOR BULB
POSITIONING.

STUB END

TEFLON

RING

LIQUID LINE ASSEMBLY

WITH BRASS NUT

DISTRIBUTOR

ASSEMBLY

Figure 21. Typical TXV Installation

1. Remove the field−provided fitting that temporary

reconnected the liquid line to the indoor unit’s liquid
line orifice housing.

2. Install one of the provided Teflon rings around the

stubbed end of the TXV and lightly lubricate the
connector threads and expose surface of the Teflon
ring with refrigerant oil.

3. Attach the stubbed end of the kit valve to the liquid line

orifice housing. Finger tighten and use an appropriately
sized wrench to turn an additional 1/2 turn clockwise
as illustrated in figure 19, or 20 ft−lb.

4. Place the remaining Teflon washer around the other

end of the TXV. Lightly lubricate connector threads
and expose surface of the Teflon ring with refrigerant
oil.

5. Attach the liquid line assembly to the TXV. Finger

tighten and use an appropriately sized wrench to turn
an additional 1/2 turn clockwise as illustrated in figure
19, or 20 ft−lb.

6. Attach the sensing bulb of the TXV in the proper

orientation as illustrated in figure 22 to the suction line
using the clamp and screws provided.

ON 7/8" AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O’CLOCK
POSITION. NEVER MOUNT
ON BOTTOM OF LINE.

12

ON LINES SMALLER THAN
7/8", MOUNT SENSING BULB
AT EITHER THE 3 OR 9
O’CLOCK POSITION.

BULB

12

BULB

BULB

BULB

SUCTION LINE

SUCTION LINE

NOTE − NEVER MOUNT ON
BOTTOM OF LINE.

Figure 22. TXV Sensing Bulb Installation

7. Remove and discard either the flare seal cap or flare

nut with copper flare seal bonnet from the equalizer
line port on the suction line.

IMPORTANT

When removing the seal nut, ensure that the copper
flare seal bonnet is removed.

SUCTION LINE

FLARE NUT

COPPER

FLARE SEAL

BONNET

MALE BRASS EQUALIZER

LINE FITTING

FLARE SEAL

CAP

OR

Figure 23. Copper Flare Seal Bonnet Removal

8. Connect the equalizer line from the TXV to the

equalizer suction port on the suction line. Finger
tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated
in figure 19.

NOTE − To prevent any possibility of water damage,
properly insulate all parts of the TXV assembly that may
sweat due to temperature differences between the valve
and its surrounding ambient temperatures.

Содержание TSA036H4N41

Страница 1: ...41 TSA048H4N41 and TSA060H4N41 AIR CONDITIONER 506083 01 03 08 Table of Contents Shipping and Packing List 1 TSA H4 Air Conditioners 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant fr...

Страница 2: ...ble 1 shows torque values for fasteners Table 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 in lb 2 NM Machine screws 10 28 in lb 3 NM Compressor...

Страница 3: ...nd use an appropriately sized wrench to turn an additional 1 6 turn clockwise as illustrated in figure 2 To Open and Close Angle Type Service Valve A valve stem cap protects the valve stem from contam...

Страница 4: ...as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench to turn an additional 1 12 turn clockwise as illus...

Страница 5: ...CONSIDERATIONS Consider the following when positioning the unit Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the install...

Страница 6: ...ne that ran from condenser to evaporator coil Refrigerant was metered into the evaporator by utilizing temperature pressure evaporation effects on refrigerant in the small RFC line The length and bore...

Страница 7: ...caps or service valve stub caps until you are ready to make connections WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubi...

Страница 8: ...nnect manifold gauge set from service ports cool down piping with wet rag and remove all wrappings Do not reinstall cores until after evacuation procedure Reinstall service caps if desired to close of...

Страница 9: ...ushing Existing System IMPORTANT The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushin...

Страница 10: ...gerant to flow into the system through the suction line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine 4...

Страница 11: ...aining Teflon washer around the other end of the TXV Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil 5 Attach the liquid line assembly to the TXV Finger...

Страница 12: ...or unit 6 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be detected NOTE Amounts of refrigerant will vary with line lengths 7 Check all joints for leak...

Страница 13: ...to break the vacuum and install a new filter drier in the system 4 Evacuate the system again Then weigh the appropriate amount of HFC 410A refrigerant as listed on unit nameplate into the system 5 Mo...

Страница 14: ...e only with copper conductors NOTE A complete unit wiring diagram is located inside the unit control box cover NOTE See unit wiring diagram for power supply connections If indoor unit is not equipped...

Страница 15: ...ine service port INDOOR COIL AIRFLOW CHECK Check indoor coil airflow using the Delta T DT process as illustration in figure 27 DETERMINING CHARGE METHOD To determine the correct charging method use th...

Страница 16: ...utdoor ambient temperature 64 F and BELOW 1 Check Liquid and suction line pressures 2 Compare unit pressures with Table 27 Normal Operating Pressures 3 Conduct leak check evacuate as previously outlin...

Страница 17: ...erant If refrigerant is added or removed verify charge using the Approach Method 64 F and BELOW 65 F and ABOVE ABOVE or BELOW F C 036 042 048 060 65 18 13 7 2 10 5 6 8 4 4 8 4 4 75 24 9 5 0 7 3 9 8 4...

Страница 18: ...7 190 9 83 246 5 98 308 2 114 385 4 129 469 5 145 572 8 37 111 4 53 150 1 68 194 1 84 250 3 99 312 7 115 390 7 130 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147...

Страница 19: ...ineering Handbook for optional accessories that may apply to this unit The following may or may not apply Timed Off Control Sound Cover Suction Line Drier Stand Off Kit Low Ambient Kit Homeowner Infor...

Страница 20: ...vides temporary heat supplied by the auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperatu...

Отзывы: