background image

Page 19

TSA*H4 SERIES

LOW PRESSURE SWITCH

TSA*H4 units are equipped with a low pressure switch that
is located in the suction line to the compressor. The switch
is a SPST, auto−reset switch that is normally closed. The
switch opens at 25 psi and closes at 40 psi.

Maintenance

Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each
cooling season, the system should be checked as follows:

WARNING

Electric shock hazard. Can cause
injury or death. Before attempting to
perform any service or maintenance,
turn the electrical power to unit OFF at
disconnect switch(es). Unit may have
multiple power supplies.

OUTDOOR UNIT

1. Clean and inspect outdoor coil (may be flushed with a

water hose). Ensure power is off before cleaning.

2. Outdoor unit fan motor is pre−lubricated and sealed.

No further lubrication is needed.

3. Visually inspect all connecting lines, joints and coils for

evidence of oil leaks.

4. Check all wiring for loose connections.

5. Check for correct voltage at unit (unit operating).

6. Check amp draw on outdoor fan motor.

UNIT NAMEPLATE: _________ ACTUAL: __________

7. Inspect drain holes in coil compartment base and

clean if necessary.

NOTE - If insufficient heating or cooling occurs, the unit
should be gauged and refrigerant charge should be
checked.

INDOOR COIL

1. Clean coil if necessary.

2. Check connecting lines, joints and coil for evidence of

oil leaks.

3. Check condensate line and clean if necessary.

INDOOR UNIT

1. Clean or change filters.

2. Blower motors are prelubricated and permanently

sealed. No more lubrication is needed.

3. Adjust blower speed for cooling. Measure the pressure

drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.

4.

Belt Drive Blowers − 

Check belt for wear and proper

tension.

5. Check all wiring for loose connections.

6. Check for correct voltage at unit. (blower operating)

7. Check amp draw on blower motor.

UNIT NAMEPLATE: _________ ACTUAL: __________

OPTIONAL ACCESSORIES

Refer to the Engineering Handbook for optional
accessories that may apply to this unit. The following may
or may not apply:

Timed Off Control

Sound Cover

Suction Line Drier

Stand−Off Kit

Low Ambient Kit

Homeowner Information

WARNING

Electric shock hazard. Can cause
injury or death. Before attempting to
perform any service or maintenance,
turn the electrical power to unit OFF at
disconnect switch(es). Unit may have
multiple power supplies.

IMPORTANT

Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface
of steel and aluminum parts and diminish
performance and longevity of the unit.

NOTE − A white residue may appear on the coil guards and
grilles on outdoor units. The residue is a non−toxic
byproduct of manufacturing the flexible coating. It can be
removed by wiping the coil guard with a cloth.

Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each
cooling season, the system should be checked as follows:

1. Make sure power is off before cleaning. Clean and

inspect outdoor coil. The coil may be flushed with a
water hose.

2. The outdoor coil is protected by an inner mesh screen

and a wire cage (see figure 33). If debris has collected
between the mesh screen and the coil and cannot be
dislodged by spraying unpressurized water from
inside coil surface to the outside, the mesh may be
removed by first removing the top of the unit which will
allow for removal of the wire cage.

3. Then, using pliers to grip the head of the push pins, pull

straight out to extract the push pins along one side of
the coil. If necessary, remove the push pins along the
back of the unit; it is usually unnecessary to fully
remove the inner mesh screen.

4. Drape the mesh screen back and wash the coil. When

all the debris has been removed from the coil, reinstall
the mesh screen by positioning it in its original position
and reinserting the push pin. No tool is required to
push the pin back into the same slot in the fins.

5. If the push pin is loose and tends not to stay in place,

brush the fins with a fin brush (22 fins/in). Line up the

Содержание TSA036H4N41

Страница 1: ...41 TSA048H4N41 and TSA060H4N41 AIR CONDITIONER 506083 01 03 08 Table of Contents Shipping and Packing List 1 TSA H4 Air Conditioners 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant fr...

Страница 2: ...ble 1 shows torque values for fasteners Table 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 in lb 2 NM Machine screws 10 28 in lb 3 NM Compressor...

Страница 3: ...nd use an appropriately sized wrench to turn an additional 1 6 turn clockwise as illustrated in figure 2 To Open and Close Angle Type Service Valve A valve stem cap protects the valve stem from contam...

Страница 4: ...as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench to turn an additional 1 12 turn clockwise as illus...

Страница 5: ...CONSIDERATIONS Consider the following when positioning the unit Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the install...

Страница 6: ...ne that ran from condenser to evaporator coil Refrigerant was metered into the evaporator by utilizing temperature pressure evaporation effects on refrigerant in the small RFC line The length and bore...

Страница 7: ...caps or service valve stub caps until you are ready to make connections WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubi...

Страница 8: ...nnect manifold gauge set from service ports cool down piping with wet rag and remove all wrappings Do not reinstall cores until after evacuation procedure Reinstall service caps if desired to close of...

Страница 9: ...ushing Existing System IMPORTANT The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushin...

Страница 10: ...gerant to flow into the system through the suction line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine 4...

Страница 11: ...aining Teflon washer around the other end of the TXV Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil 5 Attach the liquid line assembly to the TXV Finger...

Страница 12: ...or unit 6 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be detected NOTE Amounts of refrigerant will vary with line lengths 7 Check all joints for leak...

Страница 13: ...to break the vacuum and install a new filter drier in the system 4 Evacuate the system again Then weigh the appropriate amount of HFC 410A refrigerant as listed on unit nameplate into the system 5 Mo...

Страница 14: ...e only with copper conductors NOTE A complete unit wiring diagram is located inside the unit control box cover NOTE See unit wiring diagram for power supply connections If indoor unit is not equipped...

Страница 15: ...ine service port INDOOR COIL AIRFLOW CHECK Check indoor coil airflow using the Delta T DT process as illustration in figure 27 DETERMINING CHARGE METHOD To determine the correct charging method use th...

Страница 16: ...utdoor ambient temperature 64 F and BELOW 1 Check Liquid and suction line pressures 2 Compare unit pressures with Table 27 Normal Operating Pressures 3 Conduct leak check evacuate as previously outlin...

Страница 17: ...erant If refrigerant is added or removed verify charge using the Approach Method 64 F and BELOW 65 F and ABOVE ABOVE or BELOW F C 036 042 048 060 65 18 13 7 2 10 5 6 8 4 4 8 4 4 75 24 9 5 0 7 3 9 8 4...

Страница 18: ...7 190 9 83 246 5 98 308 2 114 385 4 129 469 5 145 572 8 37 111 4 53 150 1 68 194 1 84 250 3 99 312 7 115 390 7 130 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147...

Страница 19: ...ineering Handbook for optional accessories that may apply to this unit The following may or may not apply Timed Off Control Sound Cover Suction Line Drier Stand Off Kit Low Ambient Kit Homeowner Infor...

Страница 20: ...vides temporary heat supplied by the auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperatu...

Отзывы: